Model SCM Air to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 3: Specications and Ratings (continued)
Heat Pump SCM060 Series
PERFORMANCE
SCM-060 Heating Operation SCM-060 Cooling Operation
Supply
Water
Temp °F
Ambient
Temp °F
Capacity
BTU/hr
Water DP
ft WC
Watts COP
Supply
Water
Temp °F
Ambient
Temp °F
Capacity
BTU/hr
Water DP
ft WC
Watts COP
100
17 33,075 13.5 3,880 2.50
42
82 54,102 13.5 5,281 3.00
32 46,828 13.5 3,970 3.45 95 45,163 13.5 5,510 2.40
47 60,580 13.5 4,263 4.16 105 34,343 13.5 6,285 1.60
110
17 30,703 13.5 4,513 1.99
44
82 57,500 13.5 5,262 3.20
32 43,468 13.5 4,618 2.76 95 48,000 13.5 5,622 2.50
47 56,234 13.5 4,959 3.32 105 36,500 13.5 5,938 1.80
120
17 28,500 13.5 5,249 1.59
47
82 62,832 13.5 5,411 3.40
32 40,350 13.5 5,371 2.20 95 52,451 13.5 5,485 2.80
47 52,200 13.5 5,768 2.65 105 39,885 13.5 5,840 2.00
All data based upon pure water @ 12.0 GPM
SCM-060 Heating Performance
SCM-060 Cooling Performance
1.00
2.00
3.00
4.00
5.00
13.00
16,000
24,000
32,000
40,000
48,000
56,000
64,000
15 20 25 30 35 40 45 50
SCM- 060 HEAT ING PERFORMANCE
120
110
100
Coefficient of Performance
OUTDOOR AMBIENT TEMPERATURE, °F
All data based upon pure water @12.0 GPM
HEATING CAPACITY, BTU/hr
SupplyWater
Temp °F
16,000
24,000
32,000
40,000
48,000
56,000
64,000
SCM- 060 COOLING PERFORMANCE
42
44
47
1.0
2.0
3.0
4.0
80 85 90 95 100 105
Coefficient of Performance
OUTDOOR AMBIENT TEMPERATURE, °F
All data based upon pure water @12.0 GPM
SupplyWater
Temp °F