Inverter Air-to-Water Heat Pump
Parameter F (Fan Parameter)
Normally, in heating mode or cooling mode, fan will start up 10s ahead of compressor and 30s later to shut off.
F01——Max speed in heating
F02——Min speed in heating
F03——LP of suction for heating at max speed
F04——HP of suction for heating at min speed
F05——Max speed in cooling
F06——Min speed in cooling
F07——HP of exhaust for cooling at max speed
F08——LP of exhaust for cooling at min speed
F09——Manual Speed
If F09≠0, the fan will operate according to the set value of F09.
F10——Timer Mute
F11——Mute Timer Start Hour
F12——Mute Timer End Hour
F13——Mute Mode Speed
1. Fast mute function
When the fast mute function is turned on, the fan will run according to the parameter F13 if it needs to be turned on, and exit the
mute function after 8 hours. The manual operation of fast mute during the timing mute will result in the time mute failure.
2. When F10=1, enable the timing mute function.
During the time of F11-F12 (including F11, excluding F12), if the fan needs to be turned on, it will run according to the parameter
F13. If the fan needs to be turned on at other times, the speed will be controlled according to the suction pressure and exhaust
pressure.
3. During the period that the mute function is performed, if high /low voltage protection occurs in any system:
① Automatic exit fast mute function;
② Permanently exit the timer mute function, and will be restored until the power is reenergized.
F14——DC/EC Fan Rated Speed
F15——Fan Motor Type [0- [High] /1- [DC Single Fan] /2- [DC Single Fan]]