EasyManua.ls Logo

Specialty Concepts MARK-15 - OPERATION; CHECK FOR VOLTAGE DROP (OPTIONAL)

Specialty Concepts MARK-15
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION INSTRUCTIONS (continued)
16. OPERATION: - Operation of the charge controller is now fully automatic. If the
battery voltage is below the Full Charge Termination set-point (14.4 volts) and power
is available from the array, the MARK/(15,20) should start up “CHARGING”.
17. CHECK FOR VOLTAGE DROP (OPTIONAL): - Once the system is installed and
operational, a check on the connections is recommended. A poor connection will result
in a voltage loss that will distort the battery voltage reading and cause the charging to
stop too soon. To check the connections, an accurate volt-meter is required, The
MARK/(15,20) must be charging with maximum expected charge current (very sunny
conditions).
Battery Connection: - First, note the voltage at the battery. Then, immediately note
the voltage at the MARK/(15,20) battery terminals. Ideally, the difference in voltage
should be no more than ¼ volt.
Array Connection: - Next, note the voltage at the panel. Then, immediately note the
voltage at the MARK/(15,20) Array terminals. Ideally, the difference should be no
more than ½ volt.
If the voltage drop is more, suspect crimp connections that have not been soldered, in-
line fuses or fuse holders, or loose terminals. If no location of voltage drop is found,
consider using larger wires (or double up the wires) for your run.
Example: You record these readings:
Battery terminals: 13.65 volts
MARK/(15,20) battery connection: 13.95 volts “.30 volt difference too large.
Decrease voltage drop”
MARK/(15,20) panel connection: 14.10 volts
Panel(s): 14.30 volts “Connection OK”
8