3. LCD Indicators
Overload or short-circuit
protection
4. Five Load Working Modes
1.Pure light control (0): When sunlight disappears and the light intensity drops to the starting point (light control off), the controller
initiates a 10-minute delay (settable) to confirm the starting signal, and then switches on the load for operation. When sunlight emerges and the
light intensity reaches the starting point, the controller initiates a 1-minute (fixed) delay to confirm the shutting-down signal, and then shuts down
the output to stop the load's operation.
2.Light control + time control (1 to 14): The starting process is the same as pure light control. After operating for a preset period
of time (settable from 1 to 14 hours), the load stops operation automatically.
3.Manual mode (15): In this mode, the user can switch the load on or off by the keys, no matter whether it's day or night.
4. Debugging mode (16):
When the solar panel voltage is higher than the "light control off" voltage, switch off the load immediately; when the solar panel voltage is lower
than the "light control on" voltage, switch on the load immediately.
5. Normal on (17): The energized load keeps in output state.