6.4 AUTOMATIC CYCLE
Select “Automatic” from the menu;
- Set the “VACUUM TIME”, the “VACUUM TEST” and the quantity of oil and gas to be charged into
the a/c system.
It is possible to perform manually the following operations:
RECOVERY
OIL DISCHARGE
VACUUM
LEAK TEST
NEW OIL INJECTION
GAS CHARGING
If some leak is detected inside the a/c system (only if the leak test was previously set), on the display will ap-
pear the message “ERROR 2- insufficient vacuum sealing”, in this case you will have to find the leak by us-
ing a leakseeker lamp or an electronic leakseeker (accessories on request). Press “C” to exit.
If the charge is performed regularly, the display will show the quantity of charged gas.
To print out the data (for Printer version only) see the paragraph “Data printing”.
Perform the pressure control (par. 6.1):
At the end of the cycle disconnect the couplings from the a/c system and perform a manual recovery
to discharge pressure from the hoses.
PLEASE NOTE: If during the oil discharge a pressure increase occurs (> 0,5 bar), the station will go on to
the recovery phase automatically
PLEASE NOTE: If during the vacuum phase a pressure increase occurs (> 0,5 bar), the station will stop
and the display will show the message “ERROR 5” . In this case perform a recovery be-
fore proceeding.
Use the arrow keys to set values, “enter”to confirm and “C” to cancel.