Unità di comando motori MDU100
Manuale di installazione, operazione e manutenzione
Motor drive unit MDU100
Installation, Operation and Maintenance Manual

Questions and Answers

  • M
    madison87Aug 10, 2025
    Why Spirax Sarco MDU100 actuator does not receive commands and the valve is fully open?
    • B
      Breanna LucasAug 10, 2025
      If the power is on, but the actuator isn't receiving commands, and the valve is fully open, it could be due to issues with the analog signal line or the valve position potentiometer. * Check the analog input signal. * Inspect the potentiometer on the valve and its connections.
  • S
    Sue OchoaAug 15, 2025
    What to do if Spirax Sarco MDU100 actuator does not receive commands and the thermal protection is open?
    • L
      lopeztheresaAug 15, 2025
      If the power is on, but the actuator isn't receiving commands, and the valve remains in position with the yellow light on and the MDU100 thermal protection open, it indicates that the motor's thermal protection (RTV) has been triggered. If the thermal protection trips continuously, there may be a problem with the valve, motor winding, or a mechanical blockage. * Allow the motor to cool down, and if there are no rotor blockages, the unit will restart. * Reset the protection and check if the motor is short-circuited. If necessary, replace the motor. * Manually move the valve.
  • D
    Douglas GonzalezAug 20, 2025
    How to troubleshoot Spirax Sarco MDU100 when the motor doesn't move in local mode?
    • E
      Elizabeth ChristianAug 20, 2025
      If the local/remote selector is set to 'local', there's no thermal intervention, the positioner LEDs are correct, but the motor doesn't move when commanded to open/close, it could be due to problems with relays K1 and K2 or the increase/decrease selector. Check the K1 and K2 relays and the selector. If they are out of service, replace them.
  • C
    Corey GilesAug 25, 2025
    What to do if Spirax Sarco DC Drives power light is off but positioner LEDs are off?
    • D
      Dennis ReidAug 26, 2025
      If the power switch is ON, but the indicator light is OFF, and the positioner LEDs are all off, it indicates a blown fuse. Replace the F2 fuse. Check the two fuses and replace the blown ones. Check the 3 fuses and replace the blown ones. Verify the 24 Vdc power supply.
  • P
    Patrick VangAug 29, 2025
    Why Spirax Sarco DC Drives motor stays in position in remote mode?
    • E
      Eugene HarveyAug 29, 2025
      If the local/remote selector is set to remote, the positioner LEDs are correct, and the motor remains in position without thermal intervention, relays K1 and K2 may have issues. Inspect the relays and replace them if they are out of service.
  • J
    jpattersonSep 4, 2025
    What to do if Spirax Sarco MDU100 DC Drives power lamp is off but some positioner LEDs are on?
    • X
      Xavier WalkerSep 4, 2025
      If the power switch is ON, the power lamp is OFF, and some LEDs on the positioner are ON, the lamp may be broken. Replace the white lamp on the unit door.