Installation of Bearing Display Module BDM
1. Hold down A+B until all LEDs light up. The
display shows the active program(s).
2. Hold down A+B until the display flashes
”000”.
3. Press A for 'one channel mode'. The display
shows ”0XX”, where the flashing "XX" is the
number of the active program.
4. To change the program, press B repeatedly
until the desired program number is shown.
5. Press A to go to the reset setting. B toggles
between automatic and manual reset (see
below).
6. Press A to end the programming mode and
start normal operation.
3 seconds
Selects program
Programming, one channel mode
Shows active program(s)
Starts programming mode
Sets 'One channel mode',
shows active program
One channel mode, programming
When programming in 'one channel mode', the button A is used to go to the next step while the button
B is used to make changes. You can step through the whole program and check all setting by simply
pressing A.
3 seconds
Shows reset setting
Ends programming mode
Toggles between AAU
(automatic reset) and Art
(manual reset) of ALARM
Alarm reset
ALERT (yellow LED on) always has automatic reset: both the status display and relay positions are
controlled by the measured signal. This means that an alarm disappears when the measured value drops
to or below the alarm limit.
ALARM (red LED on) has the same automatic reset when 'AAU' is active. When manual reset 'Art' is
active, the status display and the relay positions are held until either A or B is pushed. This will reset the
status display and the relays if the alarm condition has disappeared.
Please note: if the incoming signal drops below 4 mA while ALARM is held, the red LED will flash instead
of the yellow LED.
Relay action in one channel mode
The relays are specified 24 V/100 mA. In one channel mode, the relay mode 'r 1' is active and can not be
changed by the user.
ALARM
red LED on
ALERT (no power)
yellow LED on
OK
green LED on
In one channel mode, the module receives the analog
signal on channel 1. Two alarm levels can be programmed
(see page 8).
Level 1 = ALERT = yellow LED is connected to Relay 1.
Relay 1 is NC = normally closed. It opens on power
failure and on alarm (value above the lower or ALERT
alarm level). Thus, it will be open when the yellow or the
red status LED is on.
Level 2 = ALARM = red LED is connected to Relay 2.
Relay 2 is NO = normally open. It closes on ALARM =
red status LED is on.
NC
NO