EasyManua.ls Logo

SPX FLOW Hankison HPR Series - Field Service Troubleshooting Guide; Common Dryer Problem Diagnosis

SPX FLOW Hankison HPR Series
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
FIELD SERVICE GUIDE
Problemsmostfrequentlyencounteredwithrefrigerateddry-
ersarewaterdownstreamofthedryerandexcessivepressure
drop.Mostcausescanbeidentiedandremediedbyfollowing
this guide.
Closed refrigeration systems are potentially
dangerous.Work on the refrigerationsystem must be done
only by a competent refrigeration mechanic. Do not release
uorocarbonrefrigerantstotheatmosphere.Allrefrigerants
mustberecoveredperEPArequirements.Donotsmokewhen
arefrigerationleakissuspected.Burningmaterialsmaydecom-
poserefrigerants,formingatoxicgasoracidsthatmaycause
serious injury and property damage. Before dismantling any
partofthedryerorcompressedairsystem,completelyvent
the internal pressure to the atmosphere.
PROBLEM SYMPTOM POSSIBLE CAUSE REMEDY
Water Downstream of
Dryer
Refrigerantcompressornot
running.
Leakinrefrigerationsystem. Contact your local distributor.
Compressor overheated.
Turndryeroff,wait30minutes;turndryeron.
(Motorthermostatself-starting)
Compressor burned out. Contact your local distributor.
Nocondensatedischargingfrom
dryer.
Failureofdrain. Dismantleandcleanstrainer.Repairorreplace
solenoid valve.
Dryerinletairtemperaturetoo
high.
Aftercoolermalfunction. Checkaftercoolerdischargetemperatureand
reducetodryerdesigncondition(120°Fmax)
Excessive Pressure
Drop Across Dryer
Lowoutletpressure. Dryerundersized(mayalsocause
waterdownstreamofdryer)
Checkairowanddryercapacity.Reduceairowor
resizeandreplacedryer.
Dryericingup.(checkatseparator) Contact your local distributor.
Color Indicator Out of
Green Zone
Indicatorinredzone. Inletairtemperaturetoohigh. Reduceaftercoolerdischargetemperaturetodesign
conditions(SeeEngineeringData).
Condenserfouledorclogged. Clean or replace condenser.
Inletairtemperaturetoohigh. Reduceaftercoolerdischargetemperaturetodesign
conditions.(SeeEngineeringData)
Highambienttemperature. Ventilatearea.
Improperadjustmentofexpansion
valve.
Removecapfromtheexpansionvalveandturnthe
screwuntiltheindicatorisinthegreenzone.
Indicatorinbluezone. Improperadjustmentofexpansion
valve.
Adjusttheexpansionvalveuntiltheindicatorisin
thegreenzone.
Lowambienttemperature. Increaseambienttemperaturetodesignconditions.

Related product manuals