iQ Control Box
28      Document # 204144  REV B  •  www.stanleyaccess.com • 1.800.7.ACCESS 
Copyright 2019, Stanley Access Technologies, LLC.
 
All rights reserved. Reproduction 
 
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
Attachment 2
iQ System Wiring Diagram
(Sheet 8 of 10)
X-Zone ST
For Security Applicaons / 1-WAY
Key DIP Switch sengs: 10 and 11 DOWN; 12, 13, 14, 15 and 16 UP. 
X-Zone ST and X-Zone (ST)
Key DIP Switch sengs: 10 and 11 DOWN; 12, 14 and 15 UP.
iQ
Remove JP301.
Set index 19 to Value = 00 (Sensor Monitoring with Threshold Control).
X-Zone T 
Key DIP Switch sengs: 11 and 12 DOWN; 13 and 15 UP.
iQ
Remove JP301.
Set index 19 to Value = 03 (Monitored 2 Sensors).
NOTE:: The X-Zone ST will replace the X-Zone (ST) in 2019.