English
8
Reader�Tamper
If�the�backplate�is�pulled�away�from�the�wall,�the�tamper�plate�remains�attached�to�the
wall�and�a�wall�tamper�condition�is�generated.�Likewise,�if�the�reader�is�removed�from�the
backplate,�a�case�tamper�condition�is�generated.
The�voltage�on�the�Tamper�line�is�normally�low.�If�case�tamper�or�wall�tamper�is�detected,
the�voltage�on�the�Tamper�line�becomes�high�and�the�reader�sounds�3�long�beeps�every�5
seconds�for�two�minutes,�then�stops.
To�clear�a�wall�tamper�condition,�reattach�the�backplate�to�the�tamper�plate.�To�clear�a�case
tamper�condition,�reattach�the�reader�to�the�backplate.
Usage
LEDs
Red Green Red�/�Green
Default Access�permitted Access�denied
Sounder
•
The�reader�sounds�4�rapid�beeps�when�it�is�powered�up�or�restarted.
•
If�specified,�the�reader�beeps�once�when�a�token�is�presented.
Cable�Lengths
PAC/�Sonitrol�door�controllers�only
Distance�from�Reader�to�ControllerCable�Gauge
PAC�2100/2200 PAC�202/512/�Sonitrol
7/0.2� 0.34mm²� 22AWG 750ft�/�250m 230ft�/�70m�*
16/0.2� 0.5mm²� 20AWG 1500ft�/�500m 230ft�/�70m�*
32/0.2� 1.0mm²� 18AWG 3000ft�/�1000m 230ft�/�70m�*