Appendix A - UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with PS161-6 output.
System Sensor
Smoke Detector/Base
Detector Type
Max Stand-by
Current (mA)
Alarm Current
(mA)
B112LP Base 0.12 36
DH100ACDC Photoelectric 0.15 0.70
DH100ACDCLP Photoelectric 0.15 0.70
DH100ACDCLPW Photoelectric 0.15 0.70
DH400ACDCI Ionization Duct 25 95
DH400ACDCP Photoelectric Duct 25 95
1112/24/D Ionization 0.05 50
1424 Ionization 0.10 41
1451 (w/B402B Base) Ionization 0.10 39
2112/24ATR Photoelectric 0.50 60/70
2112/24AITR Photoelectric 0.50 60/70
2112/24/D Photoelectric 0.05 50
2112/24T/D Photoelectric w/135o Thermal 0.05 50
2112/24TSRB Photoelectric w/135o Thermal Supervisory Relay 15 45
2312/24TB Photoelectric 0.12 50
2412 (12 volt) Photoelectric 0.12 77
2424 Photoelectric 0.10 41
2451 Photoelectric 0.10 39
2451TH (with/B402B Base) Photoelectric 0.10 39
2W-MOD Loop Test/Maintenance Mod. 30 50
4W-B (12/24 volt) Photoelectric I3 .05 23
4WT-B (12/24 volt) Photoelectric I3 w/Therm .05 23
4WTA-B (12/24 volt) I3 Photo w/Therm/Sounder .05 35
4WTR-B (12/24 volt) I3 Photo w/Therm/Relay .05 35
4WITAR-B (12/24 volt) I3 Photo w/Isolated Therm/Sounder/Relay .05 50
6424 Projected Beam 10 28.4
Beam 1224(S) Projected Beam 17 38.5
A.2 Relays
Table A-2 below lists relays compatible with PS161-6 output.
Manufacturer Model Current (mA) Manufacturer
System Sensor EOLR-1 30 System Sensor
For assistance or warranty information:
Call 1-855-365-2407 or visit
www.stanleysecurity.com/precision
Warning: This Manufacturer advises that no lock can provide complete security by itself. This lock may be defeated by forcible or technical means,
or evaded by entry elsewhere on the property. No lock can substitute for caution, awareness of your environment, and common sense. Builder’s
hardware is available in multiple performance grades to suit the application. In order to enhance security and reduce risk, you should consult a
qualified locksmith or other security professional.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Stanley PS161-6 and is the answer not in the manual?

Stanley PS161-6 Specifications

General IconGeneral
BrandStanley
ModelPS161-6
CategoryPower Supply
LanguageEnglish

Related product manuals