5.5 ANALOG MODULE
The analog module contains input circuits for phase current, operation counter,
and earth-leakage current. It also contains an eight-channel, multiplexed, ten-
bit, A/D converter and an isolated analog-output circuit. All inputs and outputs
have MOV protection against electrical transients.
Serial data are transferred to the isolated analog-output circuit through a dual-
channel optical isolator. The analog signal is scaled and buffered to provide the
required current or voltage output.
5.6 OPTION MODULES
A 50-pin bus connector on the display module accepts a backlighting, remote
input, or RS-485 communications interface module.
5.7 FIRMWARE
The FPU-16 has a two-cycle sampling interval followed by a one-cycle
calculation interval.
In each sampling interval, the multiplexed A/D converter obtains 200 samples of
the earth-fault and phase-current signals. The multiplexer sequences these four
signals so that each measurement is a digital integration of 50 samples
uniformly spaced throughout the sampling interval.