w LWZ 5-8 CS Premium / 21
I COMPONENT INV Kmin 0 500 500
MAX BOOSTER STG HTG 0 3 3
MAX FLOW TEMP HTG. °C 10 75 60
SUMMER MODE °C 10 25 17
HYST. SUMMER MODE K 1 7 4
OUTSIDE T ADJUSTMENT h 0 24 1
DUAL MODE POINT °C -20 10 -10
BOOSTER TIMEOUT min 0 60 20
OUTSIDE T CORRECTION °C -20 30 0
SUPPR TEMP MEAS s 0 120 60
DESIGN TEMPERATURE °C -25 5 -20
HEATING SYS OUTPUT SIZING % 40 100 100
DHW
DHW TEMPERATURES
DHW SET DAY °C 10 65 45
DHW SET NIGHT °C 10 65 45
DHW SET STANDBY °C 10 65 10
DHW SET MANUAL °C 10 65 45
DHW TEMPERATURE °C - - -
MIXED WATER AMOUNT
MWM SET DAY l 50 288 200 No function
MWM SET NIGHT l 50 288 150 No function
MWM SET STANDBY l 50 288 50 No function
MWM SET MANUAL l 150 288 150 No function
MIXED WATER AMOUNT l
STANDARD SETTING
HYSTERESIS K 2 10 2
MWM HYSTERESIS 50 288 50
BOOSTER TIMEOUT min 0 360 90
BOOSTER T ACTIVATE °C -20 10 -10
PASTEURISATION d 1 30 30
MAX DHW HTG DUR. h 6 12 12
PASTEURISATION TEMP. °C 10 65 30
PASTEURISATION TIME 00:00 23:45 02:00
DHW BOOSTER STAGE 0 3 3
DHW BUFFER MODE OFF| ON OFF ON OFF
MAX FLOW TEMP DHW °C 10 75 75
DHW ECO OFF| ON 0 1 1
DHW OUTPUT SUMMER % 30 100 60
DHW OUTPUT WINTER % 30 100 60
INTEGRAL SENSOR OFF| ON | CONTROL OFF
INTEGRAL SENSOR CLASS -8 8 0
2ND DHW CYLINDER OFF| ON OFF
VENTILATION
FAN CONTROL FLOW RATE | DIFFERENTIAL PRESSURE FLOW RATE
DIFFERENTIAL PRESSURE
SET DIFFERENTIAL PRESSURE Pa 20 100 60
I FACTOR Pa s m³ 1 10 2
P FACTOR Pa/m³ 1 10 2
VENTILATION STAGES
DAY STAGE 0 3 2 ( Delivered condi-
tion: 0 )
NIGHT STAGE 0 3 1 ( Delivered condi-
tion: 0 )
STANDBY STAGE 0 3 0 ( Delivered condi-
tion: 0 )
PART Y STAGE 0 3 3 ( Delivered condi-
tion: 0 )
MANUAL STAGE 0 3 2 ( Delivered condi-
tion: 0 )
VENTILATION TIMES
UNSCHED. VENT TIME STAGE 0 min 0 1000 60
UNSCHED. VENT TIME STAGE 1 min 0 1000 60
UNSCHED. VENT TIME STAGE 2 min 0 1000 60
UNSCHED. VENT TIME STAGE 3 min 0 1000 60
FLOW RATE