CODE PARAMETER UOM* TYPE MINIMUM MAXIMUM DEFAULT
/5
Select Celsius (°C) or Fahrenheit (°F)
flag C 0 1
/c1 Calibration of probe 1 °C/°F C -20 20
/c2 Calibration of probe 2 °C/°F C -20 20
St Temperature set point °C/°F F r2 r1
rd Control delta °C/°F F 20 0.1
dl Interval between defrosts hours F 0 250
dt1 End defrost temperature, evaporator °C/°F F -50 200
dP1 Maximum defrost duration, evaporator min F 1 250
d6 Display on hold during defrost - C 0 2
dd Dripping time after defrost min F 0 15
d/1 Display of defrost probe 1 °C/°F F - -