7. Start-up
Before you first start up the system install and connect it as described in the “Installation” chap-
ter.
Make sure the main switch is turned off and that the system is isolated from power mains.
Check that all power switches in the electric system have been turned off.
Check that the main electric supply cable and the terminals, including the PE terminals, are correctly connec-
ted.
Check that contactors can move freely.
Use the main switch (both on site power supply and on the unit) to switch on the control system.
Activate the control fuses one by one and the power switches for the fan. On units type AS GES activate also the
power switch of the compressor.
Check the supply voltage on all phases.
Units type AS: check the supply voltage on all phases
for the remote condenser.
Units type CW, GES: start either dry-cooler or water
chiller. Verify water circulation and temperature.
Unit type AS GES: pre-heat the compressor sump for
3-4 hours when first starting up the system or when
re-starting it after a long time out if the conditioner has
been inactive in rooms with temperatures lower than
0°C.
At this point the electronic board is powered and the single components of the system can be activated to check
for proper operation.
Set the desired supply air temperature and the desired differential set point (difference between return and supply
air temperature) on the C7000 display.
Start the climate control system by pressing the ON-OFF push-button on the display.
Units type AS GES: after about 20 minutes of opera-
tion check the sightglass for air bubbles in the liquid
pipe. If there are bubbles this may have been caused
by a leak and loss of refrigerant. Check the circuit for
leaks. Repair all leaks and refill the circuit with R410A
refrigerant as described in the previous chapter.
Units type CW, GES: check that there are no water
leakages.
Check the current that is absorbed by the compressor
(units type AS GES), fans and other optional compo-
nents, comparing these values with those indicated in
technical data.
Units type AS: check also electric consumption of the
remote condenser.
When the system is operating at normal capacity:
1) check that there are no alarms;
2) check that the fans work properly;
3) check, with the unit operating, that the power supply remains within the values indicated on the rating plate for
the unit;
Shutdown
To shut the unit down, disconnect it from all its power supplies by the corresponding isolating switches.
The ON-OFF key on the C7000 controller is only used to put the unit in stand-by. It must not be
mistaken as a safety component to turn the unit off prior to performing maintenance.