12
STULZ CyberRow
Sound Data
Sound Pressure - LpA, free field (dBA) in a 121.13 ft² (3.43m³)
room
at 3.28 (1.0m) distance
Unit
Airflow
(SCFM)
63 125 250 500 1000 2000 4000 8000
Total
dBA
NR
Value
CRS-042-_ 1500 17.4 22.1 29.0 37.1 41.9 37.0 28.7 14.2 42.0 42
CRS-084-_ 2900 21.5 49.1 52.4 55.7 54.7 53.6 49.7 31.4 65.9 55
CRS-090-_ 2900
33.7 45.1 53.4 48.1 46.9 47.6 40.9 35.6 56.4 50
CRS-091-_ 2900
33.7 45.1 53.4 48.1 46.9 47.6 40.9 35.6 56.4 50
(Note:AllsoundtestingisperformedinaccordancetoISO9614-2DeterminationofSoundPowerLevels.ISO
9614-speciesamethodformeasuringthecomponentofsoundintensitythatisnormaltoameasurement
surface. The measurement surface is chosen to enclose the noise source(s) so that the sound power level can
be determined.)
Electrical
Data
CRS-042-_ CRS-084-_
FLA (OEM Rated)
MCA MFS
FLA (OEM Rated)
MCA MFS
AR W G AR W G
COOLING ONLY
208/1/60 22.5 18.5 23.7 31.2 50 N/A
208/3/60 18.5 16.2 19.2 25 40 27.8 24.6 28.7 37.5 60
460/3/60 9.3 8.2 9.6 12.2 15 13 11.6 13.5 18.8 30
575/3/60 6.7 5.9 6.9 10.1 15 10.4 8.9 10.4 13.8 20
Electrical
Data
CRS-090-_ CRS-091-_
FLA (OEM Rated)
MCA MFS
FLA (OEM Rated)
MCA MFS
AR W G AR W G
COOLING ONLY
208/1/60 N/A N/A
208/3/60 N/A N/A
460/3/60 19 16.2 20.7 31.5 50 19 16.2 20.7 31.5 50
575/3/60 N/A N/A
ELECTRICAL AND SOUND DATA
(Note: Standard 1 KAIC rating, optional 65 KAIC rating available.)