EasyManua.ls Logo

Suburban NT-16SEQ - User Manual

Suburban NT-16SEQ
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
SUBURBAN MANUFACTURING COMPANY
676 Broadway Street
Dayton, Tennessee 37321
423-775-2131
www.RVComfort.com
INSTALLATION MANUAL
For Furnace Models
NT-16SEQ • NT-20SEQ
The design of these furnaces have been certied for installation in recreational vehicles only. In order for these furnaces to operate in conformity
with generally accepted safety regulations, the installation instructions outlined in this book must be followed. Failure to comply with the installation
instructions will void any responsibility of Suburban Manufacturing Company. Your furnace was inspected before it left the factory. If any parts are
found to be damaged, do not install the furnace. Any damages should be reported to the transportation company immediately and the appropriate
claims led.
WARNING! Improper installation, adjustment, alteration, service or maintenance can cause
property damage, personal injury or loss of life. Refer to the installation instructions and/
or owners manual provided with this appliance.
INSTALLATION INSTRUCTIONS
WARNING! Installation of this appliance must be made in accordance with
the written instructions provided in this manual. No agent, representative
or employee of Suburban or other person has the authority to change,
modify or waive any provision of the instructions contained in this
manual.
CAUTION: If possible, do not install the furnace to where the vent can be
covered or obstructed when any door on the trailer is opened. If this is not
possible, then the travel of the door must be restricted in order to provide
a 6” minimum clearance between the furnace vent and any door whenever
the door is open.
NOTE: The exhaust temperature of this furnace could discolor or warp some
materials. You should verify that the material used on the coach door, panel, or
cover will not discolor or warp from the exhaust temperature whenever any door,
panel, or cover is in the open position.
CAUTION: Due to the differences in vinyl siding, this appliance should not
be installed on vinyl siding without rst consulting with the manufacturer
of the siding or cutting the siding away from the area around the appliance
vent.
CAUTION: In any installation that has the exhaust/intake vent covered or the
minimum clearances to the room air grill reduced by some special feature
of the RV such as a slide-out, pop-up, etc. in the travel or storage mode, a
switch must be installed to insure unit is inoperable in this mode.
NOTE: These furnaces must be installed and vented as described in this manual
so that the negative pressure created by the air circulating (return air) fan cannot
affect the combustion air intake or venting of any other appliance. It is imperative
that the products of combustion be properly vented to the atmosphere and that all
combustion air supplied to burner be drawn from the outside atmosphere. (See
“Installing Vent Assembly”.)
NOTE: These furnaces shall be installed so the electrical components are
protected from water.
These furnaces will accommodate an installation depth from 21” to 27
3
/
4
”,
depending on the intake vent tube length you select. (See Figure 1.)
Please adhere strictly to the following instructions to insure proper installation and
safe operation, as well as adequate clearances for accessibility.
The efciency rating of the appliance is a product thermal efciency rating
determined under continuous operating conditions and was determined
independently of any installed system.
These furnaces are certied for use with propane/LP gas only. Gas supply
pressure for purposes of input adjustment:
Gas Minimum Maximum
Propane/LP 11” W.C.* 13” W.C.*
*Water column
In the USA, the installation must conform with local building codes. In the absence
of local building codes, refer to the latest edition of:
1-Standard for Recreational Vehicles NFPA 1192.
2-National Fuel Code ANSI Z223.1/NFPA 54.
3-The furnace must be electrically grounded in accordance with the latest
edition of the National Electrical Code NFPA 70.
4-The installation of the furnace shall be in accordance with any applicable
local codes and regulations.
In Canada, the furnace must be installed in accordance with:
1-Standard CAN/CSA Z240.0.2-08 Recreational Vehicles
2-CSA Standard CAN/CSA Z240.6.2-08/C22.2 No. 148-08 Electrical
Requirements for Recreational Vehicles.
3-Standard CAN/CSA Z240.4.2-08 Installation Requirements for Propane
Appliances and Equipment in Recreational Vehicles.
4-CAN/CGA-B149 Installation Codes
5-Any applicable local codes and regulations.
The furnace cabinet must extend through the coach cabinetry 1 3/8” as shown in
Figure 1. The 1
3
/
8
extension must be held in order to assure that the front grille will
properly attach to the furnace cabinet. Adequate clearances must be maintained
around furnace cabinet so that the unit will be accessible for servicing.
TO INSTALL THE FURNACE
1. Locate the furnace near lengthwise center of the coach. Do not install the
furnace with the vent facing toward the forward end of the coach.
2. Select a location for installation out of the way of wires, pipes, etc. that might
interfere with installation. Adhere to the following minimum clearances from the
furnace cabinet to combustible construction.
Back - 0” Top - 5/8”
Floor - 0” Sides - 5/8”
NOTE: Side and top clearances of furnace cabinet may be 0” for through the wall
installations up to a maximum of 2
1
/
2
” wall thickness (See Figure 2.)
The following minimum clearances from the warm air discharge grille to
combustible materials must be maintained: See Figure 10 for 0” clearance of
grille if framed.
Models NT-16SEQ, NT-20SEQ
Front 24” Top 1” Floor
1
/
4
Left Side 1” Right Side 8” or Left Side 8” Right Side 1”
(See Figure 8)
Part Number 204877
8-1-2011
Question and Answer IconNeed help?

Do you have a question about the Suburban NT-16SEQ and is the answer not in the manual?

Summary

INSTALLATION INSTRUCTIONS

US Installation Codes

Outlines US codes like NFPA 1192, ANSI Z223.1, and NEC for proper installation.

Canadian Installation Codes

Details Canadian standards such as CAN/CSA Z240 for RV installations.

Furnace Placement and Mounting

Guides on selecting the furnace location and initial cabinet mounting.

Reduced Front Clearance Requirements

Gas Supply Connection Procedure

Instructions for safely connecting the gas supply line.

Electrical Supply Connection Procedure

Steps for connecting the furnace to the 12-volt DC electrical system.

Thermostat Wiring Instructions

Guidance on connecting the thermostat to the furnace control.

Vent Assembly Installation Steps

Detailed instructions for installing the furnace vent system.

Vent Tube Sizing and Installation

Furnace Cabinet Mounting Details

Instructions and diagrams for securing the furnace cabinet.

Furnace Back View and Cutouts

Diagram illustrating the rear of the furnace and required openings.

Vent Cap Installation Process

Steps for correctly installing the external vent cap.

Electrical Connector Location

Furnace Wiring Diagram

A schematic illustrating the furnace's internal electrical components and connections.

Minimum Side Clearance Illustration

Visual guide showing required clearances on the sides of the furnace.

Return Air Clearance Requirements

Specifies clearances needed for proper return air flow to the furnace.

Framed Grille Clearance Guidelines

Clearances required when the furnace grille is installed within a frame.

Overview

This document describes the installation and maintenance of Suburban NT-16SEQ and NT-20SEQ furnaces, designed for recreational vehicles (RVs).

Function Description

The Suburban NT-16SEQ and NT-20SEQ furnaces are heating appliances designed for installation in RVs. They operate on propane/LP gas and a 12-volt DC negative ground electrical system. The primary function is to provide heat to the living area of the RV. The furnaces are designed to draw combustion air from the outside atmosphere and vent exhaust gases outside, ensuring that combustion air is not drawn from the living area and exhaust gases do not enter the RV.

Important Technical Specifications

  • Gas Type: Propane/LP gas.
  • Gas Supply Pressure (for adjustment purposes): Minimum 11" W.C. (water column), Maximum 13" W.C.
  • Electrical System: 12-volt DC, negative ground.
  • Electric Ignitor Energy Consumption: 0.1 amps at 12 volts DC (for NT-16SEQ and NT-20SEQ models).
  • Fuse Protection: Maximum 7.5 amps.
  • Wiring: All wires are 18 AWG unless otherwise specified. Replacement wires must have a temperature rating of at least 105°C. No. 12 gauge wire is recommended for power supply to minimize voltage drop and provide sufficient power for start-up surge.
  • Vent Tube Installation Depths:
    • X050711 (2" O.D. x 2 3/4" Special intake tube): 21" to 23 1/4" "X" dimension.
    • X050712 (2" O.D. x 5" Standard intake tube): 23 1/4" to 25 1/2" "X" dimension.
    • X050708 (2" O.D. x 7 1/4" Special intake tube): 25 1/2" to 27 3/4" "X" dimension.
    • Exhaust tube (8" x 2" O.D.) is 7 3/4" long and accommodates all approved installation depths.
  • Minimum Overlap for Vent Tubes: 1/2" minimum overlap for intake tube, 1 1/4" minimum overlap for exhaust tube.
  • Clearances to Combustible Materials (Cabinet):
    • Sides: 5/8"
    • Back: 0"
    • Floor: 0"
    • Top: 5/8"
    • Note: Side and top clearances can be 0" if installed through a wall up to 2.5" thick.
  • Minimum Clearances (Hot Air Discharge Grille):
    • NT-16SEQ, NT-20SEQ (Full Front Clearance):
      • Front: 24"
      • Left Side: 1"
      • Right Side: 8"
      • Top: 1"
      • Floor: 1/4"
    • NT-16SEQ (Reduced Front Clearance - 12"):
      • Front: 12"
      • Left Side: 8"
      • Right Side: 1"
      • Top: 1"
      • Floor: 1/4"
    • NT-20SEQ (Reduced Front Clearance - 18"):
      • Front: 18"
      • Left Side: 8"
      • Right Side: 1"
      • Top: 1"
      • Floor: 1/4"
    • Note: If the left or right side clearance is less than 8" with 12" (NT-16SEQ) or 18" (NT-20SEQ) front wall clearance, 12 square inches of additional return air is required.
  • Framed Grille Clearance: Frame can be at 0" clearance to top & sides of grille, extending 1 3/4" max. from the back side of the grille. A 1/4" bottom clearance must be maintained for return air under the unit.
  • Thermostat: Must have NO voltage output to return leg when there is no call for heat or in the "OFF" setting.
  • Duct Adapter (Optional): A 4" diameter knockout on the left side of the cabinet allows for a 4" diameter connector to provide a warm air discharge duct (not to exceed 10" in length).

Usage Features

  • Installation Location: The unit should be located out of traffic and away from furniture and draperies due to high surface temperatures. It should be installed near the center of the coach.
  • Mounting: The furnace cabinet must extend 1 3/8" through the coach cabinetry for proper front grille attachment. The furnace is secured to the floor using two screws provided in the cabinet.
  • Vent Assembly: The vent outlet must be installed in the same atmospheric pressure zone as the combustion air intake. The exhaust and intake tubes are installed from the outside, passing through the RV skin and sliding onto the furnace exhaust and intake ports. Caulking is required behind the vent cap to seal against moisture.
  • Thermostat Placement: The room thermostat should be located approximately 4 1/2 feet above the floor on an inside bulkhead, away from other heat sources. If the thermostat has an adjustable anticipator, it should be set at 0.7 amps, with adjustments made in 0.5 amp increments for longer or shorter heating cycles.
  • Electrical Connection: Connect power supply to the red (positive) and yellow (negative) wires on the right side of the furnace, observing polarity. If using a converter, it's recommended to wire it in parallel with the battery for constant voltage and to filter AC spikes/surges.
  • Gas Connection: A 3/8" flare connection is provided on the right side of the furnace for gas supply. All male joints must be treated with a sealing compound resistant to LP gas. A 1/8" NPT plug tap should be provided upstream of the gas connection for a test gauge.
  • Safety Features:
    • A safety screen or guard removed for servicing must be replaced before operation.
    • The area around the unit must be kept clear from combustible materials, gasoline, and other flammable vapors and liquids.
    • A switch must be installed in any installation where the exhaust/intake vent could be covered or obstructed (e.g., by a sliding window or pop-up top in travel mode) to ensure the unit does not operate in that mode.
    • Combustion air must not be drawn from the living area, and exhaust gases must be vented outside.

Maintenance Features

  • Inspection: The unit should be inspected before use and at least annually by a qualified service person.
  • Cleaning: More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners, and circulating air passageways of the unit be kept clean.
  • Leak Checks: All gas joints must be checked for leaks using a soap and water solution after connecting the gas supply. Never use an open flame.
  • Pressure Testing: The appliance must be disconnected from the gas supply piping system during any pressure testing of that system at pressures exceeding 1/2 PSIG. It must be isolated from the gas supply piping system during pressure testing at pressures equal to or less than 1/2 PSIG.
  • Wiring Replacement: If any original wires need replacement, they must be replaced with wiring material having a temperature rating of at least 105°C.
  • No Hi-Pot Testing: Do not hi-pot (dielectric high voltage test) the unit after installation, as this may cause component damage and void the warranty.

Suburban NT-16SEQ Specifications

General IconGeneral
BrandSuburban
ModelNT-16SEQ
CategoryFurnace
LanguageEnglish

Related product manuals