SECTION 3 PRODUCT USER MANUAL
 129
Dryer-on light is lit but
Refrigerant Compressor
does not run.
 
 
 
Clogged condenser fins
or clogged water
condenser.
 
Possible high crankcase 
temperature
 
Possible loss of phase
 
Possible low voltage caus-
ing overload trip
 
Possible failed compres-
sor
Clear fins or water
condenser of all
obstructions.
The clogged fins in the con-
denser will restrict the air pas-
sage and reduce the refrigeration 
capacity, causing high tempera-
ture in the evaporator. Same will 
occur if water condenser is 
clogged with mud or dirt. Air con-
denser and water condenser 
should be periodically checked 
and cleaned. Protect water circuit 
by an adapted filter.
Too much compressed air 
flow.
Check actual flow
through the dryer.
This dryer is designed for a maxi-
mum air flow at design condi-
tions. If too much air is pumped 
into the dryer, water removal 
capacity may not be sufficient, 
resulting in liquid carryover down-
stream. Check the rated output 
the air compressor.
Faulty electrical wiring Inspect the circuit The compressor-on light should
be wired into the refrigerant
compressor circuit. See wiring
diagram in chapter ??rawings?
of this manual.
One electrical protection 
has tripped.
Reset the protection or 
replace the blown fuse.
The dryer is protected against 
high amp draw by fuse and/or 
overload relay that can trip in 
case of need. Reset or replace 
fuse once, but do not persist  if it 
trips again, request assistance 
from a qualified refrigeration con-
tractor.
Dryer-on light is lit but
fan is not running.
Fan has to run if refriger-
ant high pressure reaches 
upper set point.
Check that compressed air 
flows through the dryer. Check 
that fan blades are free to 
move. Check the fan pressure 
switch.
Fan operates automatically to 
keep refrigerant pressure below 
the maximum value. The fan can 
stop if pressure is under
the recommended setting.
When compressor starts, 
it vibrates a lot and 
makes mechanical noise.
Compressor is slugging 
liquid refrigerant at start-
up.
Be sure the pre-heating period 
of at least4 hours is respected 
for dryers equipped with a 
crankcase heater.
Refrigerant may move between 
receivers when refrigerant com-
pressor is stopped and not 
heated, especially if stopped for a 
long time. This migration may 
cause  liquid shock (slugging) in 
valves specially on large dryers 
containing more refrigerant.
Problem Possible Cause Repair Comments