RH SERIES—HIGH TEMPERATURE SECTION 2
10
2.1 SPECIFICATIONS
Pay attention to the Minimum and Maximum
operating conditions before installing and operating
the dryer.
If your application does not match the above criteria,
contact your Sullair distributor and they will be able to
provide the right dryer for your application.
2.2 INTRODUCTION
The RH series of Non-cycling Refrigerated Air Dryers
are specially designed for compressed air systems
that do not use an after cooler. The hot compressed
air from the compressor enters the downstream
receiver tank where condensed moisture is removed
with an automatic drain. The hot saturated air is then
passed directly into the RH series of dryers.
RH series of non-cycling refrigerant compressed air
dryers have been designed to remove water vapor
from industrial compressed air that is free of reactive
contaminants like ammonia, gaseous acid, dust, rust
or any other chemical or mineral products capable of
reacting or clogging the heat exchanger. The dryers
are designed and recommended for indoor
applications.
Normal Operating Pressure
175 PSIG
Normal Operating Temperature
200 Deg. F
Normal Ambient Temperature
100 Deg. F
Maximum Operating Pressure
230 PSIG
Minimum Operating Pressure
80 PSIG
Maximum Ambient Temperature
120 Deg. F
Minimum Ambient Temperature
40 Deg. F
Maximum Operating Temperature
240 Deg. F