EasyManua.ls Logo

Sullair SD-600 - Section 5 Dryer Flow Capacity and Purge Adjustment; 5.1 Dryer Flow Capacity

Sullair SD-600
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION, START-UP & MAINTENANCE MANUAL
MODEL NO.: SD-220 TO SD-600- DDS OPTION
REV 0 – May 24,,.2001
27
SECTION 5 DRYER FLOW CAPACITY AND PURGE ADJUSTMENT
5.1 DRYER FLOW CAPACITY
Model Selection Chart
Average Inlet Air Flow (SCFM)
Based upon 100 F Inlet Air Temperature Inlet Air Pressure
MODEL
Max. Inlet
Air Pressure
(Psig)
80 90 100 110 120 130 140
SD-220
150 175 202 220 253 272 293 310
SD-300
150 230 265 300 340 362 390 416
SD-400
150 305 352 400 438 470 510 544
SD-500
150 378 435 500 550 590 635 675
SD-600
150 485 555 600 700 760 810 850
SD-820
150 640 735 820 890 960 1035 1105
SD-1050
150 830 960 1050 1215 1325 1410 1590
SD-1200
150 980 1095 1200 1305 1415 1520 1615
SD-1450
150 1110 1280 1450 1510 1700 1825 1950
SD-1710
150 1325 1515 1710 1810 1945 2080 2230
SD-2000
150 1530 1720 2000 2100 2220 2390 2530
SD-2350
150 1875 2165 2350 2700 2930 3150 3350
SD-2750
150 2085 2400 2750 2990 3225 3490 3720
SD-3400
150 2775 3080 3400 3650 3950 4250 4540
1. Higher pressures available as an option. Consult factory
2. Based on – 40 F PDP, 10 Minute NEMA cycle, activated alumina and average inlet
air flow.
5.2 CORRECTION FACTOR FOR INLET TEMPERATURE
TEMPERATURE
DEGREES F
80 90 100 105 110 115 120
Correction Factor 1.1 1.1 1.0 0.83 0.69 0.565 0.455
To correct for an inlet temperature other than 100 F multiply dryer capacity by the
temperature correction factor listed above.

Table of Contents