F-24
6.6.2 Run/stop control with frequency setting signals
: Operation starting frequency
: Operation starting frequency hysteresis
• Function
The Run/stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title Function Adjustment range Default setting
Operation starting frequency 0.0- (Hz) 0.0
Operation starting frequency hysteresis
0.0- (Hz) 0.0
0A B 100%
Frequency command value
+
-
The inverter begins accelerating after
the frequency setting signal has reached
point B.
Deceleration begins when the frequency
setting signal decreases below point A.
6.7 DC braking
6.7.1 DC braking
: DC braking starting frequency
: DC braking current
: DC braking time
• Function
A large braking torque can be obtained by applying a direct current to the motor. These parameters
set the direct current to be applied to the motor, the application time and the starting frequency.
[Parameter setting]
Title Function Adjustment range Default setting
DC braking starting frequency 0.0- (Hz) 0.0
DC braking current 0.0-100 (%) 50
DC braking time 0.0- 20.0 (sec) 1.0