15
Terminal Functions
Terminal Functions
Main Circuit Terminals
Terminal nameSymbol
Monitor terminal (frequency, current, etc.)
Common terminal for monitor and frequency command
External DC power supply
Intelligent input terminals:
Select from forward run command, reverse run command, multispeed
commands, 2-stage acceleration / deceleration command,free run stop,
external trip, jogging, analog input selection, software lock, reset.
Intelligent output terminals:
Select from match run, overload , alarm,
frequency match, and frequency detect.
Alarm output terminals (IC contact (relay) output)
Common terminal for
frequency command
Frequency command
input (current command)
Frequency command
input (voltage command)
Power supply for
frequency command
PWM output
–
DC24V, Max.30mA
DC10V
DC0–10V(Variable by parameter)
Input impedance 10kΩ
DC4–20mA (Variable by parameter)
Input impedance 250Ω
–
Open collector output
L level at operation (ON)
DC27V, Max.50mA
Ground to prevent electric shock
and reduce noise.
Connect the DC reactor for harmonic
suppression. Power factor improvent
(Remove the shorting bar when
connecting a DC reactor.)
Connect the motor
Connect the input power supply
Ground connection
terminal
DC reactor connection
terminals
Inverter output terminals
Main power supply
input terminals
P,P1
U,V,W
R,S,T
Control Circuit Terminal
Symbol Terminal Name Remarks
FRQ
COM
PCS
RST
3DF
2DF
RR
FR
+V
VRF
IRF
COM
DRV
UPF
OM
AL2
AL1
AL0
Input / Monitor signalFrequency command
(Note 1)
Output signal
Alarm output
Alarm terminal
Ground
Control circuit
terminals
Main circuit
terminals
M4(M3.5) 9(7.1)
M2 (press-tight type)
–
M3 (press-tight type)
–
M4 –
Terminal
width
Terminal screw
diameter
[Main circuit terminals] [Control circuit terminals]
Main circuit terminals Front case (right open)
Ternimal section cover (left open)
Control circuit terminals
(Note 1) The maximum frequency command is 9.8 V when the voltage input is 0-10 VDC, and 19.6 mA when the current input is 4-20 mA.
(Note 2) The reset terminal cannot be changed to [Operation with (SW) Open].
current command value is output. When either voltage or current is selected,
be sure to allot the analog input selection to the multifunctional input terminal.