Quick User Manual 6 Troubleshooting
23
The internal
temperature of inverter
is too high.
moment for inverter recovery.
2. Check whether there is enough space for
convection.
3. Check whether the inverter is in direct
sunlight.
4. Check whether the fan is normal.
Replace it if necessary.
5. Clean the air inlets.
6. If the fault persists, please contact
Sungrow.
Relay fault on the grid
side.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept.
The insulation
resistance is low.
(ISO-flt)
1. Check whether there is a reliable inverter
grounding line.
2. Check whether the positive and negative
of PV panels is short-circuited with ground
lead.
3. Wait a moment for inverter recovery.
4. If the fault occurs repeatedly, contact
Sungrow Service Dept.
Leakage current
sampling fault.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept.
Inner
under-temperature
fault.
The ambient
temperature inside the
inverter is too low.
The inverter will recover once the ambient
temperature rises above -25℃.
Open-loop inverter
self-test fault.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept.
Phase current
sampling fault.
The slave DSP detects
that the grid voltage
exceeds the protective
value.
1. Check the grid voltage.
2. If the grid voltage exceeds the
permissible range of inverter protection
parameters, ask utility grid company for
solution.
3. If the grid voltage is within the permissible
range, contact Sungrow Service Dept.