6 Troubleshooting Quick User Manual
24
Code
Description
Troubleshooting
054
The slave DSP detects
that the grid frequency
exceeds the protective
value.
1. Check the grid frequency.
2. If the grid frequency exceeds the
permissible range of inverter protection
parameters, ask utility grid company for
solution.
3. If the grid frequency is within the
permissible range, contact Sungrow Service
Dept.
056
The slave DSP detects
that the leakage
current exceeds the
protective range.
1. Check whether there is a grounded fault
of the PV string.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept.
059
Communication alarm
between master DSP
and slave DSP.
1. Wait 1 minute for inverter recovery.
2. If the fault persists, contact Sungrow
Service Dept.
061
Alarm for no inverter
type setting.
Contact Sungrow Service Dept.
070
Fans are defective
Stop the inverter and disconnect the AC &
DC cables. Check whether the fan duct has
been blocked. If not, replace fans.
084
Warning for reverse
cable connection of the
Sungrow Meter.
1. Check whether the power cable
connections are correct.
2. If Existing Inverter is set to ON via
LCD menu, check and ensure that its rated
power is correctly set.
3. For Sungrow single-phase meter, check
whether the CT clamp of the 1-phase
sensor is correctly placed.
085
Mismatched software
version.
Please contact Sungrow Service Dept.
100
The AC output current
exceeds the upper
limit.
1. The inverter will resume if the output
current falls below the protection value.
2. If the fault persists, please contact
Sungrow Service Dept.
101
Grid over-frequency.
The grid frequency
exceeds the protective
value, which is higher
than the protective
value of error 008.
1. Check the grid frequency.
2. If the grid frequency exceeds the
permissible range of inverter protection
parameters, ask utility grid company for
solution.
3. If the grid frequency is within the
permissible range, contact Sungrow Service
Dept.
102
Grid under-frequency.
The grid frequency is
below the protective
value, which is lower
than the protective
value of error 009.

Table of Contents

Other manuals for Sungrow SG2K-S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG2K-S and is the answer not in the manual?

Sungrow SG2K-S Specifications

General IconGeneral
BrandSungrow
ModelSG2K-S
CategoryInverter
LanguageEnglish

Related product manuals