DC Connection Area
figure 6-1 DC inout n(n≤24)
figure 6-2 DC inout n(n>24)
figure 6-3 DC connection area with energy storage system ports
No. Description
DC+ DC positive cable connection area
DC- DC negative cable connection area
ESS Energy storage system port
Cable Requirements
• The maximum cross-sectional area of the aluminum/copper cable is 400mm
2
/750Kcmil.
• Fasten the wiring terminal with the bolts in the scope of delivery. And the torques are
shown in following table.
Bolt Torque
M12×55 60~70N.m/531~619.1lbf.inch
Cable Connection Steps