XLINK 500/100 Operations & Maintenance Manual page # 35
below. WS/DIN#1 is used for the frequency as it can handle low-level AC as well as high-level DC
pulses for speed.
* A 1.0 MOhm resistor needs to be placed from VREF (or SIGNAL GROUND) to AZ SIG. This
ensures that the value always goes to 355 (or 0 with SIGNAL GROUND) when the potentiometer
is in the open region.
Setup two measurements for the RMYoung – one for the direction and one for the speed.
Setup for Direction Measurement
Measurement Type: Analog
Analog Type: 0-5A
Equation: X/VREF*355 {converts to degrees}
Setup for Speed Measurement
Measurement Type: Digital
Digital Type: Frequency 1 or Frequency 2 (amplified version only)
DC high or AC low: AC low level (for unamplified RMYOUNG)
Slope: