ThermShield Standard Square/Rectangular Installation Guide
2
Swegon reserves the right to alter specications. 20210615 - L00010
Application Installation Method
Rigid wall installation (mortar sealing)
Page
Rigid wall installation (mineral wool sealing)
Page
Rigid wall installation (Fire Batt)
Page
Flexible wall installation (mortar sealing)
Page
Flexible wall installation (mineral wool sealing)
Page
Flexible wall installation (Fire Batt)
Page
Rigid oor/ceiling installation (mortar sealing)
Page
Rigid oor/ceiling installation (Fire Batt)
Page
Suspension for mortarless oor installation
Page
Suspension for mortarless ceiling installation
Page
Suspension for mortarless installation close to ceiling
Page
Battery assembly installation x & X
Page
Battery assembly installation (oor/ceiling) x & X
Page
Battery assembly installation x
Page
Minimal separation distance installation
Page
• For full classications please refer to our Declaration
of Performance (DoP), which can be found on our
website.
• The methods in this manual should be followed to
ensure a CE-marked installation.
• The instructions are based on the tested method using
Actionair ThermShield re/smoke dampers.
• Our ThermShield dampers are designed to be
used with re separating elements to maintain re
compartments. The ThermShield is an actuated failsafe
close damper with low smoke leakage, often referred
to in the industry as a Fire/Smoke damper.
• Under the Fire Damper Product standard BS EN 15650
our Fire Damper products are tested to BS EN 1366-2
and classied under BS EN 13501-3.
CE Installation Method Overview