We reserve the right to make changes without any prior notice.Translation from original instructions
2.2.6 Operationwithwatertotheevaporatoratlowtemperature
With temperatures below 5°C, it is mandatory to work with water and anti-freeze mixtures, and also change the safety devi-
ces (anti-freeze, etc.), which must be carried out by qualied authorised personnel or by the manufacturer.
The glycol percentage by weight is determined based on the desired temperature of the chilled water (see table).
Minimum ambient temperature or liquid
outlet temperature (°C)
0 -5 -10 -15 -20 -25 -30 -35 -40
Freezing point (°C) -5 -10 -15 -20 -25 -30 -35 -40 -45
Antifreeze % by weight
Ethylene glycol 6 22 30 36 41 46 50 53 56
Propylene glycol 15 25 33 39 44 48 51 54 57
If ambient temperatures are expected to be lower than the freezing point of water, it is essential to use an-
ti-freeze mixtures in the above-mentioned percentages.
2.2.7 Operationinheatpumpmodewithlowtemperaturewater
The standard units are not designed to operate in heat pump mode with water temperatures that are too low (refer to the
Techical Catalogue for the limits).
In order to operate below this limit, the unit could require structural modications.
If required, please contact our company.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Swegon BlueBox Zeta Rev Series and is the answer not in the manual?

Swegon BlueBox Zeta Rev Series Specifications

General IconGeneral
BrandSwegon
ModelBlueBox Zeta Rev Series
CategoryChiller
LanguageEnglish

Related product manuals