[8] Model Dh400 Air Duct Smoke Detector Specifications
Description
HVAC air duct mounted ionization or photoelectronic smoke detector for 2-wire alarm systems.
Environmental Limits
Temperature: 32° to 120° F
0° to 49° C
Humidity: 10% to 93% R.H. non-condensing
Air Velocity: 500 to 4000 ft./min.
1.5 to 20.3 m/sec.
Test Features
Magnetic test switch, MOD400R test module, RTS451 Remote Test Station.
Mechanical Specifications
Length: 14.5 inches 37 cm
Width: 5 inches 13 cm
Depth:(installed) 4 inches 10 cm
Weight: 3.5 pounds 1.6 kg
Terminals
Captive universal terminal screws with sems plates accept wire sizes of 14 gauge or smaller. The screws will withstand 10
in-lbs of tightening torque without damage.
Accessories
M02-04-00 Replacement Test Magnet
RA400Z Remote Annunciator alarm LED
RTS451/RTS451KEY Remote Test Station, test switch with alarm and power LEDs
CRT400 Cover Removal Tool (Ion only)
F36-05-00 Replacement Air Filter (two per package)
MOD400R Sensitivity Test Module
P48-21-00 Replacement End Plug for inlet sampling tube
R59-18-00 Replacement Calibrated Test Card (for Photo units only)
RS14 Replacement Screen, Ion
RS24 Replacement Screen, Photo
A2650-01 Replacement Installation Kit (mounting hardware)
Sampling (Inlet) Tubes
TUBE OUTSIDE DUCT WIDTH
ST-1.5 1 to 2 feet (0.3 to 0.6 m)
ST-3 2 to 4 feet (0.6 to 1.2 m)
ST-5 4 to 8 feet (1.2 to 2.4 m)
ST-10 8 to 12 feet (2.4 to 3.7 m)
Exhaust Tube Extension
A2440-00 5.75 in. (14.6 cm.) additional
D400-14-00 12 I56-554-05