I56-0022-000
INSTALLATION AND MAINTENANCE INSTRUCTIONS
ENGLISH
L-Series with LED
Indoor Selectable-Output
Horn Strobes and Strobes
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
LED L-series Indoor Horn Strobes and Strobes — P/N I56-0022-000 8/25/2023 1
Manual is for use with the following models:
Horn Strobes
Standard Wall Mount Horn Strobes: P2RLED, P2RLED-B, P2WLED, P2WLED-B, P2RLED-P, P2WLED-P, P2RLED-SP, P2WLED-SP
Compact Wall Mount Horn Strobes: P2GRLED, P2GRLED-B, P2GWLED, P2GWLED-B
Standard Ceiling Mount Horn Strobes: PC2RLED, PC2RLED-B, PC2WLED, PC2WLED-B
2-Wire Strobes
Standard Wall Mount Strobes: SRLED, SRLED-B, SWLED, SWLED-B, SRLED-P, SWLED-P, SRLED-SP, SWLED-CLR-ALERT, SWLED-ALERT*
Compact Wall Mount Strobes: SGRLED, SGRLED-B, SGWLED, SGWLED-B
Ceiling Mount Strobes: SCRLED, SCRLED-B, SCWLED, SCWLED-B, SCWLED-CLR-ALERT, SCRLED-P, SCWLED-P
Language designators: “-B” are bilingual (English/French). “-P” are plain versions (no wording). “-SP” are marked “FUEGO”
*Amber lenses are for use in UL applications.
Table of Contents
Section 1: Introduction .................................................................................................................................................. 2
1.1 Product Specifications .......................................................................................................................................................2
1.2 Dimensions and Mounting Options ...................................................................................................................................2
1.3 Before Installing ................................................................................................................................................................2
1.4 General Description ..........................................................................................................................................................2
1.5 Fire Alarm System Considerations ....................................................................................................................................3
1.6 System Design ..................................................................................................................................................................3
Section 2: Configurations for Notification Appliances ............................................................................................... 4
2.1 Available Tones .................................................................................................................................................................4
2.2 Available Candela Settings ...............................................................................................................................................4
2.3 Current Draw and Audibility ratings ...................................................................................................................................5
Section 3: Installation .................................................................................................................................................... 7
3.1 Wiring and Mounting .........................................................................................................................................................7
3.2 Wiring Diagrams ................................................................................................................................................................7
3.3 Install Back Box .................................................................................................................................................................7
3.4 Install Mounting Plate and Appliance ................................................................................................................................7
3.5 Remove a Ceiling Model Appliance ..................................................................................................................................8
3.5.1 Mounting Drawings ........................................................................................................................................................8
3.6 Tamper Screw .................................................................................................................................................................10
3.7 Test Points ......................................................................................................................................................................10
Question and Answer IconNeed help?

Do you have a question about the System Sensor P2RLED and is the answer not in the manual?

Summary

Introduction to L-Series Horn Strobes and Strobes

Product Specifications

Details regarding operating temperature, humidity, flash rate, voltage, and wire gauge.

Dimensions and Mounting Options

Provides dimensions for wall and ceiling mounted products and compatible mounting accessories.

Before Installing

Advises on consulting reference guides and adhering to safety codes before installation.

General Description

Describes the L-Series notification appliances and their features for life safety.

Fire Alarm System Considerations

Outlines requirements for temporal coded signals and compliance with fire alarm codes.

System Design

Discusses system designer responsibilities for current draw, voltage drop, and wiring.

Configuring Notification Appliances

Available Tones

Explains the selection of 8 different horn tones and volume settings using a rotary switch.

Available Candela Settings

Details the selection of 7 different candela settings for strobe output via a rotary switch.

Current Draw and Audibility Ratings

Lists maximum strobe current draw and horn strobe current draw/sound output by candela rating.

Installation Procedures

Wiring and Mounting Guidelines

Covers electrical code compliance, wire stripping, and connecting wires to terminals.

Wiring Diagrams

Provides wiring diagrams for 2-wire horn strobes and strobes, including shorting spring feature.

Install Back Box

Instructions for attaching back boxes to walls/ceilings and selecting knockouts.

Install Mounting Plate and Appliance

Guides on attaching the mounting plate and securing the appliance to it.

Remove a Ceiling Model Appliance

Details the process for removing ceiling-mounted appliances using a captive screw and button.

Mounting Drawings

Visual guide illustrating installation of wall and ceiling mount devices and surface mount back boxes.

Tamper Screw

Describes replacing the standard captive screw with a Torx screw for tamper resistance.

Test Points

Explains the use of diagnostic test points for measuring device voltage.

Summary

Introduction to L-Series Horn Strobes and Strobes

Product Specifications

Details regarding operating temperature, humidity, flash rate, voltage, and wire gauge.

Dimensions and Mounting Options

Provides dimensions for wall and ceiling mounted products and compatible mounting accessories.

Before Installing

Advises on consulting reference guides and adhering to safety codes before installation.

General Description

Describes the L-Series notification appliances and their features for life safety.

Fire Alarm System Considerations

Outlines requirements for temporal coded signals and compliance with fire alarm codes.

System Design

Discusses system designer responsibilities for current draw, voltage drop, and wiring.

Configuring Notification Appliances

Available Tones

Explains the selection of 8 different horn tones and volume settings using a rotary switch.

Available Candela Settings

Details the selection of 7 different candela settings for strobe output via a rotary switch.

Current Draw and Audibility Ratings

Lists maximum strobe current draw and horn strobe current draw/sound output by candela rating.

Installation Procedures

Wiring and Mounting Guidelines

Covers electrical code compliance, wire stripping, and connecting wires to terminals.

Wiring Diagrams

Provides wiring diagrams for 2-wire horn strobes and strobes, including shorting spring feature.

Install Back Box

Instructions for attaching back boxes to walls/ceilings and selecting knockouts.

Install Mounting Plate and Appliance

Guides on attaching the mounting plate and securing the appliance to it.

Remove a Ceiling Model Appliance

Details the process for removing ceiling-mounted appliances using a captive screw and button.

Mounting Drawings

Visual guide illustrating installation of wall and ceiling mount devices and surface mount back boxes.

Tamper Screw

Describes replacing the standard captive screw with a Torx screw for tamper resistance.

Test Points

Explains the use of diagnostic test points for measuring device voltage.

Overview

This document provides installation and maintenance instructions for the System Sensor L-Series with LED Indoor Selectable-Output Horn Strobes and Strobes. These devices are designed for life safety notification in indoor applications and are available in standard and compact versions for both wall and ceiling mounts.

Function Description:

The L-Series devices serve as public mode notification appliances, alerting occupants to a life safety event through both audible (horn) and visible (strobe) signals. Two-wire horn strobes and strobes are listed to ANSI/UL 464/ULC-S525 (horn) and ANSI/UL 1638/ULC-S526 (strobe) requirements. Additionally, two-wire amber ALERT strobes are available as private mode notification appliances, intended to alert trained personnel to investigate a life safety event, and are listed to ANSI/UL 1638 (Private mode) for UL applications (not listed for Canadian applications).

These devices are designed for use in 24VDC systems and can be activated by a compatible fire alarm control panel or power supply. They come enabled with System Sensor synchronization protocol, requiring connection to a power supply capable of generating synchronization pulses, a FACP NAC output configured to System Sensor synchronization protocol, or the use of a synchronization module. System Sensor wall 2-wire horn strobes and strobes are electrically backward compatible with previous generations of notification appliances.

Important Technical Specifications:

  • Operating Temperature: 32°F to 120°F (0°C to 49°C)
  • Humidity Range: 10 to 93% Non-condensing
  • Strobe Flash Rate: 1 flash per second
  • Nominal Voltage: Regulated 24 VDC
  • Operating Voltage Range: 16 to 33V (24V nominal)
  • Input Terminal Wire Gauge: 12 to 18 AWG
  • Dimensions (Standard Wall Mount): Length 5.67" (144 mm), Width 4.7" (119.4 mm), Depth 2.07" (52.6 mm)
  • Dimensions (Compact Wall Mount): Length 5.27" (133.7 mm), Width 3.45" (87.8 mm), Depth 2.07" (52.6 mm)
  • Dimensions (Standard Ceiling Mount): Diameter 6.83" (173.5 mm), Depth 2.07" (52.6 mm)
  • Mounting Options:
    • Standard 2-Wire Indoor Products: 4" x 4" x 1½", Single Gang, Double Gang, 4" Octagon, SBBRL/WL (wall), SBBGRL/WL (wall)
    • Compact 2-Wire Indoor Products: Single Gang, SBBGRL/WL (wall)
    • Ceiling Mounted Products: 4" x 4" x 1½", Single Gang, Double Gang, 4" Octagon, SBBCRL/WL (ceiling)

Usage Features:

  • Selectable Output: The devices offer 8 field-selectable tone and volume combinations for the horn, and 7 field-selectable candela settings for the strobe.
  • Tone Selection: Tones are selected using a rotary switch on the back of the product. Available tones include Temporal 3 (high/low volume), Non-Temporal (high/low volume), 3.1 KHz Temporal 3 (high/low volume), and 3.1 KHz Non-Temporal (high/low volume). The Temporal 3 pattern complies with ANSI and NFPA 72 for standard emergency evacuation signaling.
  • Candela Setting: Candela output is selected via a rotary switch on the back of the product. The setting can be verified through a small window on the front of the unit. Available candela ratings for wall mounts include 15, 30, 75, 95, 110, 135, 185 cd, and FCP (future). For ceiling mounts, 15, 30, 75, 95, 115, 150, 177 cd, and FCP (future) are available.
  • Wiring and Mounting: All wiring must comply with National Electric Code (UL applications), Canadian Electric Code (ULC applications), and local codes. Wire sizes up to 12 AWG (2.5 mm²) can be used with the mounting plate.
  • Shorting Spring Feature: The mounting plate includes a shorting spring between terminals 2 and 3, enabling system continuity checks of field wiring before appliances are installed. This spring automatically disengages when the product is installed, facilitating supervision of the final system.
  • Back Box Installation: Junction boxes are mounted per industry standards. Surface mount back boxes can be secured directly to the wall or ceiling, with optional use of a grounding bracket. Specific mounting holes are designated for ceiling horn strobes/strobes (STR) and speakers/speaker strobes (SPK).
  • Knockouts: Threaded knockouts are provided for 3/4 inch and 1/2 inch conduit adapters. Rear entry knockouts for 3/4 inch and 1/2 inch are also available. V500 and V700 raceway knockouts are provided for low and high profile applications, respectively.
  • Mounting Plate and Appliance Installation: The mounting plate is attached using Philips head screws. The appliance hooks onto grooves on the mounting plate and is secured with a single mounting screw.
  • Language Designators: Models with "-B" are bilingual (English/French), "-P" are plain versions (no wording), and "-SP" are marked "FUEGO". Amber lenses are for use in UL applications.

Maintenance Features:

  • Testing and Maintenance: The notification appliance must be tested and maintained according to NFPA 72 requirements for UL applications or CAN/ULC S536 for ULC applications.
  • Tamper Screw: For tamper resistance, the standard captive screw can be replaced with a separately ordered Torx screw (T15 Torx #6-32, 5/8" SCREW-TMPR-50).
  • Test Points: L-Series devices include diagnostic test points for easy access to measure device voltage with a digital voltage meter without removing the device from the wall or ceiling. Positive and negative probes are inserted into the respective test points.
  • Protective Dust Cover: If the product is not immediately installed, a protective dust cover should be used to prevent contamination of the wiring terminals on the mounting plate.

System Sensor P2RLED Specifications

General IconGeneral
Operating Voltage24 VDC
Nominal Voltage24 VDC
Operating Temperature32°F to 120°F (0°C to 49°C)
LED IndicatorYes
Flash Rate1 Hz
Humidity Range10% to 93% non-condensing
Sound OutputNot applicable
Detection Pattern (Ceiling Mount)360 degrees
Detection Pattern (Wall Mount)180 degrees
ComplianceCSFM