Horn selections using 3-position DIP switch on horn/
strobe (refer to Figure 3):
Note: When powered from a FWR supply, the horn will be
modulated (turned on and off) by 120Hz causing it
to sound different than if powered by a DC supply.
High/Low Volume
ON=High Volume, OFF=Low Volume
Note: The low volume setting of some tones must NOT be
used for public mode applications when the device
D900-28-00 3 I56-1796-008R
HORN
(+)
(–)
(+)
(–)
E
O
L
(+)
(–)
(+)
(–)
HORN/STROBE
STROBE ONLY
TWO WIRE SYSTEM
ANY MIX OF MODELS
WIRED FOR TANDEM
OPERATION
HORN
SYNCHRONIZATION MODULE
MDL
(+)
(–)
(+)
(–)
E
O
L
(+)
(–)
(+)
(–)
HORN/STROBE
STROBE ONLY
TWO WIRE SYSTEM
ANY MIX OF MODELS
WIRED FOR TANDEM
OPERATION
(+)
(–)
(+)
(–)
(+)
(–)
FOUR WIRE SYSTEM
COMBO MODELS
WIRED FOR INDEPENDENT
OPERATION
(HORN CAN BE TURNED OFF
AT THE PANEL WHILE STROBES
CONTINUE TO OPERATE)
E
O
L
(+)
(–)
(+)
(–)
(+)
(–)
E
O
L
S
T
R
O
B
E
C
O
M
B
O
H
O
R
N
H
O
R
N
S
T
R
O
B
E
Figure 6: Any combination of models powered by
a 4-wire circuit to provide independent horn and
strobe operation (remove factory installed jumpers,
see Figure 8)
NOTE: Strobes must be powered continuously for horn
operation.
System Operation Synchronized Devices:
Figure 4b: Any combination of models powered by a
2-wire circuit:
System Operation Non-Synchronized Devices:
Figure 4a: Any combination of models powered by a
2-wire circuit:
FROM:
FACP, MODULE
OR PREVIOUS
DEVICE
TO NEXT
DEVICE OR
EOL
+
Strobe +
Strobe – Horn –
Horn +
TANDEM OPERATION
HORN/STROBE COMBO
FACTORY
INSTALLED
JUMPERS
Figure 5: Horns and strobes powered in tandem
NOTE: Supply power must be continuous for proper
operation.
Figure 7: Horns and strobes powered independently
(horn operated on coded power supply)
NOTE: Strobes must be powered continuously for horn
operation.
FROM:
FACP, MODULE (MDL)
OR PREVIOUS
DEVICE
Break wire as shown for
supervision of connection.
DO NOT allow stripped wire
leads to extend beyond switch
housing. DO NOT loop wires.
TO NEXT
DEVICE OR
EOL
INDEPENDENT OPERATION
HORN AND STROBE
TO NEXT
DEVICE OR
EOL
STROBE +
HORN +
STROBE +
STROBE –
STROBE
HORN –
HORN
HORN +
FACTORY INSTALLED
JUMPER WIRES REMOVED
NOTE: STROBES MUST
BE POWERED CONTINUOUSLY
FOR HORN OPERATION.
Figure 3: Horn Factory Default Setting
The factory default setting is High, Temporal 3, and
Electromechanical tone.
Low
OFF ON
Temporal
Electromech.
DIP Switch
Factory
Default
High
Non-Temporal
3000Hz
Base (rear)
is powered from a 12-volt panel. Refer to the Sound
Output Guide on the previous page.
Temp/Non-Temp
ON=NON-Temporal, OFF=Temporal
3KHz/Electromechanical
ON=3KHz, OFF=Electromechanical
Tone pattern override options using compatible panels:
The Selectable Output Horn/Strobe may be commanded
to override the horn selection. Horns and strobes may be
overridden to the patterns listed below:
1. Continuous EM
2. Temporal EM
3. Double March Time EM (240 strokes/min.)
4. March Time EM (120 strokes/min.)
5. Canadian EM (20 strokes/min.)
6. Strobe Disable
7. Strobe Enable
For complete details, refer to panel Installation Manual.
A0110-00
A0111-00
A0113-00
A0112-00
A0114-00
Check terminal polarity before wiring. For proper operation, make sure the correct wire
polarity is applied to the unit.
WARNING