Connection of fan motor and set-up manual for frequency converter |
12-5
For ECblue 3 ~ types and when connecting 1 ~ types between two outer conductors, only all-current sensitive fault
current circuit breakers (type B) are allowed (
EN 50 178, Art. 5.2).
Residual-current-operated protective devices
Terminal Function / connection
L1, N, PE
Mains connection for 1 ~ types (observe the line voltage indicated
rating plate).
L1, L2, L3, PE
Mains connection for 3 ~ types (observe the line voltage indicated
rating plate).