Connection of fan motor and set-up manual for frequency converter |
12-7
LED Code Relays K1
1
Cause
11 x
de-energized, 11 - 14 interrupted
Error motor start
12 x
de-energized, 11 - 14 interrupted Line voltage too low
13 x
de-energized, 11 - 14 interrupted Line voltage too high
14 x
de-energized, 11 - 14 interrupted Error Peak current
17 x
de-energized, 11 - 14 interrupted Temperature alarm
1
K1: programmed function at factory: Fault indication not inverted
output |