54 SysAer
Main
menu Q0
Item
Screen
code
Parameter Unit Min Fact. Max Description / Note
SERVICE
Communication
PG Protocol
Bacnet /
DirectConn. /
Modbus /
Lon / Ana.
Modem /
GSM Modem
/ Prog. Load
Modbus
Modbus needs a supervisor as bus master. Lon is a propietary protocol. Analog
modem is for standard analog modem. GSM is for GSM modem. Load is for software
loading with specific tools.
PH
Identification address - 0 1 32 See the communication part.
Baud rate bps 1200 9600 19200
Modem
configuration
PI
Maximum numbers - 1 1 4
Displayed only if Analog Modem is selected for the protocol. The unit modem can
call consecutively a maximum of 4 phone numbers at each alarm appearance.
View number - 1 1
Max.
num.
Allows to set each phone number
Ring number - 0 3 9 Displayed with GSM. Number of rings before the modem connection
Phone number - - - - With GSM and Analog Modem
Modem password - 0000 0000 9999 Password needed to connect to the unit modem
PJ
Ring number - 0 3 9 Displayed with Analog Modem. Number of rings before the modems connection
Modem type Tone/Impulse Tone
SMS PK SMS text - - - -
Text that will appear on each alarm SMS, in addition to the standard screens, with
the hour and date of appearance, alarm code and explanation.
PLAN network PL
Enable N/Y N
PLAN is to connect directly up to 31 units plus 1 display with not necessarily a
super-visor, to share On/OFF, mode, setpoint... between a head unit and the others.
This screen is only available on the Master unit. See the multi RoofTops installation
part.
Units number - 1 2 31 Number of units connected to the Plan network. Only on the Master unit
Configuration
Disp. Only /
MasterSlave
Disp.
Only
General Plan network configuration, available on the Master unit (with the PLAN
address 1). With Display only, one display on the Master unit 1 gives the possibility
to navigate through all the connected units. With Master/Slave, in addition, all the
units will run in the same way: ON/OFF, Summer/Winter, Setpoint... It is always
possible to have a specified configuration for each unit if the "Master" is in Master/
Slave.