8Maintenance
Warning
Inordertoavoidelectricalshock,reorotherdamagethatmightoccurinconnectionwithfaultyuse
andoperationoftheunit,itisimportanttoconsiderthefollowing:
Thesystemmustbeinstalledaccordingtotheinstallationinstructions.
Insulatemainssupplybeforeserviceorcleaningoftheheatrecoveryunit.
Makesurethelterismountedinitsplacebeforerunningthesystem.
Maintenancemustbeperformedaccordingtotheinstructions.
8.1Changingairlters
Indicatedasltertobechangedinthecontrolpanel,1-2timesperyearorasnecessary
Thebagltercannotbecleanedandmustbechangedasnecessary.Newlterscanbeorderedfrom
Systemair.
Operationtimebetweenlterchangesmustbere-setafterlterchange,seeAlarmsettings,Alarmlimits,
ServicealarmintheControlpanel.
InitialpressuredropforTA-450toTA-3000isapprox.60Paand70PaforTA-4500.Thenalpressurefor
allsizesis200-220Pa.
8.2Checkingthefan
Checkthefan(B)onceayear.
Fig.6Internalcomponents
Eveniftherequiredmaintenance,suchaschangingofltersiscarriedout,dustandgreasemayslowly
buildupinsidethefan.Thiswillreducetheefciency.
Thefanmaybecleanedwithaclothorasoftbrush.Donotusewater.Whitespiritcanbeusedtoremove
accumulationswhichareotherwisedifculttoremove.Allowdryingproperlybeforeuse.
TA450-4500
OperationandMaintenanceInstructions
132616
22
SystemairSverigeAB