EasyManuals Logo

Taco SR502 User Manual

Default Icon
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #77 background imageLoading...
Page #77 background image
75
Wiring Taco 24VAC Electric Water Feeder to Taco LF Series 24VAC Low Water Cutoff
or 24VAC McDonnell & Miller or Hydrolevel Low Water Cutoffs
Taco LFx024x
Taco EWF024
NC H N GND P
BURNER
CIRCUIT
HOT
NEUTRAL
HNLW
24 V AC
CIRCUIT
21P2
Hydro level
400, 500, 600, & 700
NHB
McDonnell & Miller
PS-802/852-24
NOTE:
Wiring shown only for control
and burner circuits of the same
voltage. Some terminal designations
are not in their actual order on the
LW COs.
** May be factory installed on
some LW COs
INSTALLED
JUMPER **
COMNO
P1A
CW
Wiring Taco 120VAC Electric Water Feeder to Taco LF Series 120VAC Low Water Cutoff
or 120VAC McDonnell & Miller or Hydrolevel Low Water Cutoffs
NC NO H N GND P
BURNER
CIRCUIT
HOT
NEUTRAL
HNLW
120 V AC
CIRCUIT
NHWB
McDonnell & Mill er
PS-801/851-120
w/Red & Green LEDs
1 245
McDonnell & Mill er
PS-801/851-120 w/Red &
Am ber LEDs, S eries 750
21P2 A
Hydro level
450, 550, 650, & 750
Taco LFx120x
Taco EWF120
NOTE:
W
iring shown only for control
and burner circuits of the same
voltage. Some terminal designations
are not in their actual order on the
LW COs.
** May be factory installed on
some LW COs
INSTALLED
JUMPER **
COM
C
3
P1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Taco SR502 and is the answer not in the manual?

Taco SR502 Specifications

General IconGeneral
Zones2
Frequency60 Hz
Relay TypeSPDT
MountingWall mount
Input Voltage120 VAC
Output Voltage24 VAC
Enclosure TypePlastic
Terminal TypeScrew terminal