54
Istruzioni per l’installazione / Installation instructions
Rev. 3.1 - 29.04.09 - IT (originali) / EN (Translations from original instructions)
Open Drive - Mod. 03A ÷ 460A
S.p.A.
INSTALLAZIONE / INSTALLATION
5
Open drive
Fusibili ultra-rapidi (A)
Ultra-Fast Fuses (A)
Tensione (AC)
Voltage (AC)
I2 T massimo (A2s)
I2 T maximum (A2s)
03 5-15 480 340
07 10-20 480 1200
12 15-25 480 1200
15 20-35 480 1200
22 25-35 480 1200
32 40-63 480 1200
40 50-63 480 2750
48 50-63 480 3900
60 80-100 480 3900
70 80-125 (*) 480 7500
90 100-140 (*) 480 9000
110 125-160 (*) 480 18000
(*) La corrente nominale del fusibile deve essere maggiore della corrente nominale di linea.
(*) The fuse rated current must be greater than the line rated current.
CARATTERISTICHE FUSIBILI PER LA LINEA DI INGRESSO / FEATURES OF INPUT FUSES
150 160-200 480 62500
175 200-250 480 62500
220 250-315 480 160000
250 315-350 480 160000
310 350-400 480 562500
370 400-450 480 562500
460 500 480 562500
TAB. 17
(Fusibili utilizzati / Fuses used)