Note: S1–S4, HDI are the upper terminals on the control
board and P05.12 can be used to set the function of
S5–S8
0: No function
1: Forward rotation operation
2: Reverse rotation operation
3: 3-wire control operation
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Operation pause
9: External fault input
10: Increasing frequency setting (UP)
11: Decreasing frequency setting (DOWN)
12: Cancel the frequency change setting
13: Shift between A setting and B setting
14: Shift between combination setting and A setting
15: Shift between combination setting and B setting
16: Multi-step speed terminal 1
17: Multi-step speed terminal 2
18: Multi-step speed terminal 3
19: Multi- stage speed terminal 4
20: Multi- stage speed pause
21: ACC/DEC time 1
22: ACC/DEC time 2
23: Simple PLC stop reset
24: Simple PLC pause
25: PID control pause
26: Traverse Pause (stop at the current frequency)
27: Traverse reset (return to the center frequency)
28: Counter reset
29: Torque control prohibition
30: ACC/DEC prohibition
31: Counter trigger
32: Reserve