Teco Installation and Maintenance Manual 
TEFC Squirrel Cage Induction Motors 
Teco Electric and Machinery Company 
Manual Number: IOM ~ TEFC Rev.01 
3.4.  INSTALLATION. 
 
3.4.1.  Site conditions for motor installation: 
Standard site conditions for installation of motors are as follows: 
a.  Ambient temperature: -20
0
C~40
0
C. 
b.  Humidity: Relative humidity below 90% RH for totally enclosed type. 
c.  Elevation: Below 1000 metres. 
d.  Should the installation be in an industrial zone, it should be free of explosive 
gases and liquids. 
e.  Foundation should be strong so as not to induce vibration. 
 
3.4.2.  Ventilation and Space. 
a.  Installation should be well ventilated. 
b.  The area should be large enough to facilitate heat dissipation and 
maintenance. 
 
3.4.3.  Foundation. 
Use rigid and solid sole plate or common bed as the foundation. 
 
3.5.  MOUNTING. 
 
3.5.1.  An adequate motor support (which is the responsibility of others) is very 
important. It must have sufficient rigidity to maintain alignment between 
the motor and its driven load. Inadequate or improperly designed motor 
supporting structures can lead to serious vibration and alignment problems. 
 
3.6.  COUPLING & ALIGNMENT. 
 
Two pole motors and motors larger than Frame 315M must not be coupled to 
the driven equipment by means other than direct connection. 
Please refer to TECO if belt connection is to be used.