12
2.3.2 General Wiring Diagram (for standard S type)
Notes:
*1:Use SW5 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multi-function
digital input terminals S1~S7.
*2:Use SW3/SW4 to switch between voltage (0~10V) and current (4~20mA) input for Multi-function analog input 1/2
(AI1/AI2). Besides please also check parameter 04-00 for proper setting.
*3:
When using the open collector for multi-function digital input, it doesn’t need resistance because of built-in pull-up resistance.
*4:Run Permissive input SF1 and SF2 is a normally closed input. This input should be closed to enable the inverter
output. To activate this input remove the jumper wire between SF1/ SF2 and SG.
*5:AO1/AO2 default setting is 0~+10V. Use SW1/SW2 to switch between voltage (0~10V) and current (4~20mA)
output. Besides please also check parameter 04-19 for proper setting.
*6:When using the open collector for pulse output of DO2, the recommend pull-up resistance is 200Ω.