APP 3
Appendix Instructions for UL
Field Wiring Terminals
All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper connections that
are to be made to each terminal and indicate that copper conductors, 75 °C cooper wire are to be used
Drive Short-Circuit Rating
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow will
not rise above value. Please see electrical ratings for maximum voltage and table below for current.
Branch circuit protection was provided by semiconductor fuse (JFHR2/8) refer to below table for details, the drive controller and
overcurrent protection device must be integrated within the same overall assembly.
Recommended Input Fuse Selection
Fuse ype
Drive Model E710
Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
200 V Class Single/Three-
Phase Drives
2P5 Bussmann FWC-16A10F 600V 16
A
201 Bussmann FWC-20
A
10F 600V 20
A
202 Bussmann FWC-32
A
10F 600V 32
A
203 Bussmann 50FE 700
V
50
A
205 Bussmann 50FE 700
V
50
A
208 Bussmann 63FE 700
V
63
A
Fuse Type
Drive Model E710 Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
400 V Class Three-Phase
Drives
401 BussmannFWC-10
A
10F 600V 10
A
402 BussmannFWC-16A10F 600V 16
A
403 BussmannFWC-16A10F 600V 16
A
405 BussmannFWC-25
A
10F 600V 25
A
408 Bussmann 40FE 700
V
40
A
410 Bussmann 50FE 700
V
50
A
Suitable for use on a circuit capable of delivering not more than ( A ) RMS symmetrical amperes for ( Hp ) Hp in 240 / 480 V class