15
■Type S
220V : 202~208HP/440V : 403~410HP
Table 3 Control terminal definition(Type S)
Type Terminal Terminal Function
Digital
input
signal
S1 Multifunction Input Terminal
S2 Multifunction Input Terminal
S3 Multifunction Input Terminal
S4 Multifunction Input Terminal
S5 Multifunction Input Terminal
S6 Multifunction Input Terminal
S7
Multifunction Input Terminal/ Pulse command input,
Bandwidth: 32KHz
24V
power
supply
24V Digital signal SOURCE point (SW6 switched to SOURCE )
24VG
Common terminal of Digital signals
Common point of digital signal SINK ( SW6 switched to SINK )
Caution
• Maximum output current capacity for terminal 10V is 20mA.
• Multi-function analog output AO1 and AO2 are used for an analog output meter. Do not use these outputs
for feedback control.
• Control board’s 24V and +10V are to be used for internal control only, Do not use the internal power-supply to
power external devices.
Type Terminal Terminal Function
Analog
input
signal
+10V Positive power for external speed potentiometer
AI1 Multi-function analog input terminal (0~10V)/(4-20mA)
GND Analog signal ground terminal
E Shielding wire’s connecting terminal (Ground)
Analog
output
signal
AO1 Multi-function analog output terminal(0~10V)/(4-20mA )
AO2 Multi-function analog output terminal(0~10V)/(4-20mA )
GND Analog signal ground terminal
Digital
output
D01 Multi-function(open collector transistor) output
DOG Open collector transistor digital ground
Relay
output
R1A
Relay A contact (multi-function output terminal)
R1B
Relay B contact (multi-function output terminal)
R1C
Relay contact common terminal,
Safety
Functions
F1
On: normal operation.
Off: stop.
(Jumper wired between SF1/ SF2 and SG has to be removed by using external
contact to stop.)
F2
SG
Safety command common terminal
RS-485
A
RS485/MODBUS
B
SGND
Grounding to earth
Shield the connecting terminal