30
**: Before to set up 00-32 Application, it should do
initialized setting (parameter 13-08) first. When
setting 00-32, the I/O port function changed
automatically. To avoid accident, be sure to confirm
the I/O port signal of inverter and external terminal
control.
*** If parameter 00-27 is set to ND mode, group 02 motor
1 parameter will automatically adjust to more than 1
class of it.
If parameter 00-27 is set to HD mode, group 02 motor 1
parameter will automatically adjust to the same class
of it.
It is suggested that parameter 00-27 be set first
before motor performs auto-tuning because the
parameter will make the motor parameter
automatically be changed.
***** If the maximum output frequency of motor is over
300HZ,the frequency resolution is changed to 0.1Hz.
Group 01: V/F Control Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
01-00
V/F Curve
Selection
0~FF F *3
01-01 Reserved
01-02
Maximum
Output
Frequency of
Motor 1
4.8~599.0
50.0/
60.0
*8
01-03
Maximum
Output
Voltage of
Motor 1
200V: 0.1~255.0 -
*8
400V: 0.2~510.0 -
575V: 0.1~670.0 -
690V: 0.1~804.0 -
01-04
Middle Output
Frequency 2
of Motor 1
0.0~599.0 0.0
01-05
Middle Output
Voltage 2 of
Motor 1
200V: 0.0~255.0
0.0 *8
400V: 0.0~510.0
575V: 0.0~670.0
690V: 0.0~804.0
01-06
Middle Output
Frequency 1
of Motor 1
0.0~599.0 3.0
01-07
Middle Output
Voltage 1 of
Motor 1
200V: 0.0~255.0
*
*8
400V: 0.0~510.0
575V: 0.0~670.0
690V: 0.0~804.0
01-08
Minimum
Output
Frequency of
Motor 1
0.0~599.0
VF:-
VF+PG:-
SLV:0.5/0.
6
SV:0.1
PMSV:0.1
PMSLV:9.
0
SLV2: 1.0
01-09
Minimum
Output
200V: 0.0~255.0
-
*8
400V: 0.0~510.0
-
575V: 0.0~670.0
Group 01: V/F Control Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Voltage of
Motor 1
690V: 0.0~804.0
01-10
Torque
Compensatio
n Gain
0.0~2.0 0.5 *1
01-11
Selection of
Torque
Compensatio
n Mode
0: Torque
Compensation
Mode 0
0
1: Torque
Compensation
Mode 1
01-12
Base
Frequency of
Motor 1
4.8~599.0
50.0/
60.0
*8
01-13
Base Output
Voltage of
Motor 1
200V: 0.0~255.0 -
*8
400V: 0.0~510.0 -
575V: 0.0~670.0 -
690V: 0.0~804.0 -
01-14
Input Voltage
Setting
200V: 155.0~255.0
-
*8
400V: 310.0~510.0
-
575V: 540.0~670.0
-
690V: 648.0~804.0
-
01-15
Torque
Compensatio
n Time
0~10000 200
01-16
Maximum
Output
Frequency of
Motor 2
4.8~599.0
50.0/
60.0
*8
01-17
Maximum
Output
Voltage of
Motor 2
200V: 0.1~255.0 -
*8
400V: 0.2~510.0 -
575V: 0.1~670.0 -
690V: 0.1~804.0 -
01-18
Middle Output
Frequency 2
of Motor 2
0.0~599.0 0.0
01-19
Middle Output
Voltage 2 of
Motor 2
200V: 0.0~255.0
0.0
400V: 0.0~510.0
575V: 0.0~670.0
690V: 0.0~804.0
01-20
Middle Output
Frequency 1
of Motor 2
0.0~599.0 -
01-21
Middle Output
Voltage 1 of
Motor 2
200V: 0.0~255.0
KVA
400V: 0.0~510.0
575V: 0.0~670.0
690V: 0.0~804.0
01-22
Minimum
Output
Frequency of
Motor 2
0.0~599.0
-
01-23
Minimum
Output
Voltage of
Motor 2
200V: 0.0~255.0
KVA
400V: 0.0~510.0
575V: 0.0~670.0
690V: 0.0~804.0
01-24
Base
Frequency of
Motor 2
4.8~599.0
50.0/
60.0
*8

Related product manuals