LED display Possible solutions
GF
Ground fault
Replace motor.
Check the motor wiring.
Disconnect motor and try
running inverter.
Check resistance
between cables and
ground.
Reduce carrier frequency.
OV
Over voltage
Increase deceleration
time
Reduce input voltage to
comply with the input
voltage requirements or
install an AC line reactor
to lower the input voltage.
Remove the power factor
correction capacitor.
Use dynamic braking unit.
Replace braking
transistor or resistor.
Adjust speed search
parameters.
UV
Under voltage
Check the input voltage.
Check input wiring.
Increase acceleration
time.
Check power source
Replace pre-charge
contactor
Replace control board or
complete inverter.
IPL input phase
loss
Check input wiring / faster
screws.
Check power supply.
OPL output
phase loss
Check output wiring /
faster screws.
Check motor & inverter
rating.
OH1
Heatsink
overheat
Install fan or AC to cool
surroundings.
Replace cooling fan.
Reduce carrier frequency.
Reduce load / Measure
output current
OL1
Motor overload
Check V/f curve.
Check motor rated
current
Check and reduce motor
load, check and operation
duty cycle.
OL2
Inverter overload
Check V/f curve.
Replace inverter with
LED display Possible solutions
larger rating.
Check and reduce motor
load, check and operation
duty cycle.
OT
Over torque
detection
Check over torque
detection parameters (08-
15 / 08-16).
Check and reduce motor
load, check and operation
duty cycle.
UT
Under torque
detection
Check under torque
detection parameters (08-
19 / 08-20).
Check load / application.
run
Switch for
Motor1/Motor2
Revise the sequence
control and switch motor
in top time.
OS
Over speed
Check ASR parameters
group 21.
Check PG parameters
Check overspeed
parameters 20-20/20-12.
PGO
PG
Open circuit
Check PG wiring.
Check PG power-supply.
Make sure brake is
released.
DEV
Speed
deviation
Check load
Make sure brake is
released.
Check PG wiring.
Check PG parameters
20-23/20-24.
Increase Acceleration /
deceleration time.
CE
communication
error
Check connection
Check host computer /
software.
FB
PID feedback
loss
Check feedback wiring
Replace feedback
sensor.
STO
Safety switch