Chapter 1 Safety Precautions 
1-2 
1.1.2 During Power up 
  Danger 
zThe inverter still has control power immediately after power loss. When the power is re-
supplied, the inverter operation is controlled by F41. 
zThe inverter operation is controlled by F04 and C09 and the status of (FWD/REV RUN 
switch) when power is re-supplied. (F39 /F40) Power loss ride through / Auto reset after 
fault). 
 
1. When F04=000, the inverter will not auto restart when power is re-supplied. 
2. When F04=001 and operation switches (FWD/REV RUN) is OFF, the inverter will not 
auto restart when power is re-supplied. 
3. When F04=001and operation switch ON and C09=000, the inverter will auto restart 
when power is re-supplied. Please turn OFF the run ( start) switch to avoid damage to 
machine and injury to personnel before the power is re-supplied. 
zWhen C09=000 (direct start on power up), please refer to the description and warning for 
C09 (Page 4-27) to verify the safety of operator and machine. 
 
1.1.3 Before operation 
   Caution 
Make sure the model and inverter capacity match the F00 setting (Page 4-12). 
 
1.1.4 Leakage current  
Warning 
  Warning! EV series built in Filter type leakage current can exceed the IEC standard limit 
of 3.5mA. Please ground the inverter as shown in figures 3.5 and 3.6. 
 
Operation with ungrounded supplies: 
1.  Filtered inverters CANNOT be used on ungrounded supplies. 
2.  Unfiltered inverters can be used on ungrounded supplies. If any output phase is shorted to 
ground, the inverter may trip with OC.(over current trip) 
 Operation with Residual Current Device(RCD): 
1.  A filtered inverter with the trip limit of the RCD is 300mA  
2.  The neutral of the supply is grounded, as is the inverter. 
3.  Only one inverter is supplied from each RCD.