INDOOR UNIT INSTALLATION
Drainage ports
By default, the drain hose is attached to
the left-had side of the unit (when you
are facing the back of the unit).
However, it can also be attached to the
right-hand side.
CONNECT DRAIN HOSE
1. To ensure proper drainage, attached
the drain hose on the same side that
your refrigerant piping exits the unit.
2. Attach drain hose extension (not
supplied) to the end of the drain hose.
3. Wrap the connection point firmly with
Teflon tape to ensure a good seal and
to prevent leaks.
4. For the section of the drain hose that
remain indoors, wrap it with foam pipe
insulation to prevent condensation.
5. Remove the air filter and pour a small
amount of water into the drain pan to
make sure that water drain from the
unit smoothly.
PLUG THE UNUSED DRAIN HOLE
To prevent unwanted leaks you must plug
the unused drain hole with the rubber plug
provided.
NOTE ON DRAIN HOSE PLACEMENT
Make sure to arrange the drain hose properly.
DO NOT kink the drain hose.
DO NOT create a water trap.
DO NOT put the end of drain hose in
water or a container that will collect water.
ELECTRICAL WIRING WORK
A
WARNING
Before performing any electrical or wiring
work, turn off the main power and read the
instructions carefully.
If there is a serious safety issue with the
power supply, stop work immediately.
Explain your reasoning to the client, and
refuse to install the unit until the safety
issue is properly resolved.
The unit must be hardwired to the
switchboard with a weather proof
isolation switch fitted in close proximity
to the outdoor unit, that disconnects all
poles and has a contact separation of at
least 1/8in
(3mm). The qualified electrician must
install an appropriate RCD/circuit
breaker at the switchboard.
The air conditioner should have its own
dedicated circuit. Do not connect
another appliance to that outlet.
All wiring must comply with the latest
Australian Wiring Rules AS/NZS 3000
and must be installed by a licensed
electrician.
All electrical connections must be made
according to the Wiring Diagram located
on the panels of the indoor and outdoor
units.
Power voltage should be same
as rated voltage. Insufficient power
supply can cause malfunction, electrical
shock, or fire.
24