compound gauge
Low pressure valve
Valve protective caps
Pressure hose
Pressure gauge
High pressure valve
Charge hose
High pressure valve
Low pressure valve
Vacuum pump
Service port
Manifold gauge
EVACUATION INSTRUCTIONS
Close the low pressure valve of the 
manifold gauge and turn off the 
vacuum.
Hold the pressure for 5 minutes, make 
sure that the rebound of compound 
gauge pointer does not exceed 
0.005MPa.
Open the low pressure valve 
counterclockwise for 1/4 turn with 
hexagonal wrench to let a little 
refrigerant fill in the system, and close 
the low pressure valve after 5 seconds 
and quickly remove the pressure hose.
Check all indoor and outdoor joints for 
leakage with soapy water or leak 
detector.
Fully open the low pressure valve and 
high pressure valve of the outdoor unit 
with hexagonal wrench.
Reinstall the protective caps of the 
service port, low pressure valve and 
high pressure valve of the outdoor unit.
Reinstall the valve cover.
A 
WARNING
Air and foreign matter in the refrigerant 
circuit can cause abnormal rises in 
pressure, which can damage the air 
conditioner, reduce its efficiency, and 
cause injury. Use a vacuum pump and 
manifold gauge to evacuate the refrigerant 
circuit, removing any non-condensable gas 
and moisture from the system.
EVACUATION INSTRUCTIONS
Before using the manifold gauge and 
vacuum pump, read their operation 
manuals to familiarize yourself with how to 
use them properly.
1. Use a spanner to remove the
protective caps from the service port,
low pressure valve and high pressure
valve of the outdoor unit.
2. Connect the pressure hose of
manifold gauge to the service port on
the outdoor unit low pressure valve.
3. Connect the charge hose from the
manifold gauge to the vacuum pump.
4. Open the low pressure valve of the
manifold gauge and close the high
pressure valve.
5. Turn on the vacuum pump to vacuum
the system.
6. The vacuum time should not be less
than 15 minutes, or make sure the
compound gauge indicates -0.1 MPa
(-76 cmHg)
7.
8.
9.
10.
11.
12.
ADDING REFRIGERANT
Standard Pipe 
Length
Pre-charged 
5 m
(Pipe Length - Standard Pipe Length) x *A / m
*A
 = 15g for TSO26H3DVJT & TSO35H3DVJT
*A = 16g for TSO52H3DVJT & TSO72H3DVJT
*A = 40g for TSO88H3DVJT 
Additional Refrigerant
Min. Pipe 
Length
Max. Pipe 
Length
Max. 
Difference  
In Level
3 m             15 m           10 m
31