- 17 -
ELT
Failed to the
Capacity
Module
1 Sudden over current
2 Short circuit of the output or
grounding
3 Bad aeration or failed the fan
4 Failed the capacity bridge
1 Refer to error code OC
2 Check the connection
and the wire
3 Improve aeration or
replace the fan
OH
Over Heat
in Capacity
Module
1 Go beyond the requirement
2 Bad aeration or failed the fan
3 Failed to Detective circuit of
temperature
1 Improve the environment
2 Improve aeration or
replace the fan
OL
Over load of
Motor
1 Disarrangement of V/F curve
2 Too low voltage
3 Run with low speed and high
torque for a long time
4 Set improper over loading
coefficient of the motor
5 The motor is blocked or too
high torque
1 Correct V/F curve
2 Check the input power
3 Select a specialized
inverter
4 Check the set parameters
5 Select a suitable motor
6 Check the connection
EMS
Failed to the
External
1 Failed to terminals of the
external equipment
1) Check the terminals
CPUE
Magnetic
disturbance
1Taking serious disturbance 1Push STOP/RESET button
-.E.r
Failed to
EPROM
1 Taking serious disturbance of
EPROM in reading / writing
2 Failed EPROM
1Push STOP/RESET button
STOP
Emergency
stop
1) locked the emergency stop
1Push STOP/RESET button
twice to unlock the
emergency stop