F0 group - Basic parameters
Code
Parameter Settings Default
F000
Frequency setup
0: Digital
1: Keyboard POT
2: Analog
0
*1
F001
Main frequency 0.0 ~ 400.0Hz 50Hz
F002
Operation setup
0: Keyboard
1: IO terminal
0
F004
Maximum running
Frequency
50.0 ~ 400.0Hz
50Hz
*60Hz
F005
Rated frequency of motor
50 Hz 50 Hz
F006
Rated voltage of motor 220V 220 V
F008
Voltage of torque
compensation
0-30 6
F012
Acceleration time 0.1 ~ 3600s 10s *0.5s
F013
Deceleration time 0.1 ~ 3600s 10s *0.5s
F014
Upper frequency limit 0.0 ~ 400Hz 50Hz
F015
Lower frequency limit 0.0 ~ F014 0Hz
F1 group c Tool parameters
Code
Parameter Settings Default
F105
Stop mode
0: Speed down
1: Coast
0
F106
Start frequency of DC
braking
0 ~ 10Hz 6 Hz
F107
Start voltage of DC
braking
0 ~ 15% 10%
F109
Forward /Reverse
compensation time
0.0s 0s
F116
Deviation Frequency 0.0Hz
F117