15
NT579-NT579 RS485
TECSYSTEM SHANGHAI
Address
HI
(10)
Address
LO
(10)
Data HI Data LO Note 1
Note
2
R: read
W:write
RW:
read/
write
0 1
2’compl.
sign
2’compl.
Ch L1 tem-
perature
from
20° to
230
R
0 2
2’compl.
sign
2’compl.
Ch L1
maximum
temperature
from 1°
to 220
R
0 3
2’compl.
sign
2’compl.
Ch L1tem-
perature
alarm set
point
from 1°
to 220
RW
0 4
2’compl.
sign
2’compl.
Ch L1 tem-
perature
trip set
point
from 1°
to 220
RW
0 5
2’compl.
sign
2’compl.
Ch L1 tem-
perature
Fan on set
point
from 1°
to 220
RW
0 6
2’compl.
sign
2’compl.
Ch L1 tem-
perature
Fan off set
point
from 1°
to 220
RW
0 7
2’compl.
sign
2’compl.
Ch L2 tem-
perature
from
20° to
230
R
0 8
2’compl.
sign
2’compl.
Ch L2
Maximum
temperature
from 1°
to 220
R